8 expansion devices
Items
Analogue Input (AD)
Voltage Input
Current Input
Analogue Input Range DC0
~
5V, 0
~
10V
DC0
~
20mA, 4
~
20mA
Max Input Range
DC±18V
DC0
~
40mA
Analogue Output
Range
-
Digital Input Range
-
Digital Output Range
14 bits binary (0
~
16383)
Distinguish Ratio
1/16383(14Bit); the convert data is stored in PLC in form of Hex. (14Bit)
(14Bit)
PID Output Value
0
~
K4095
Integral precision
0.8%
Convert Speed
20ms/CH
Power Supply
DC24V±10%, 100mA
0V
24V
C1
C0
AI0
VI1
C2
AI2
VI3
AI3
C3
VI2
A11
VI0
CH
NAME SIGNAL
CH
NAME SIGNAL
CH0 AI0
Current analogue input CH1 AI1
Current analogue input
VI0
Voltage analogue input
VI1
Voltage analogue input
C0
COM of CH0
C1
COM of CH1
CH2 AI2
Current analogue input CH3 AI3
Current analogue input
VI2
Voltage analogue input
VI3
Voltage analogue input
C2
COM of CH2
C3
COM of CH3
-
24V
+24V power supply
0V
COM of power supply
Specification
2
Terminal Arrangement
3
4CH analogue input: voltage and current input selectable; Voltage input range is 0
~
5V, 0
~
10V selectable, current input range is 0
~
20mA
、
4
~
20mA selectable;
14 bits high precision analogue input;
As the special module, 7pcs XC-E4AD can be connected to one XC series PLC main unit;
XC-E4AD module support PID auto tune function;
Содержание XC Series
Страница 1: ...WUXI XINJE ELECTRIC CO LTD XC series PLC hardware User manual Data No PC01 20110106 3 3 ...
Страница 4: ......
Страница 41: ...3 System Structure Analog Output QD QD1000 QD1031 16 channels Module s Value D D8320 D8329 ...
Страница 43: ...3 System Structure Please install the products according to chapter 2 1 1 3 Installation Environment ...
Страница 49: ...5 Input Specifications and Wiring Methods 5 2 DC Input Signal AC Power Supply Type DC Input Signal 1 ...
Страница 51: ...5 Input Specifications and Wiring Methods ...
Страница 125: ...Appendix special soft device list 1 If you change special FLASH memory it will take into effect after restart the PLC ...