8 expansion devices
8-3-8
.
XC-E3AD4PT2DA
Items
Analogue Current Input
(AD)
Temperature Input
(PT)
Analogue Voltage
Output (DA)
Analogue input
DC0
~
20mA, 4
~
20mA
PT100
-
Temperature
testing range
-
-100~350
℃
-
Max input range
DC0
~
40mA
-
-
Analogue output
range
-
-
DC0~5V,
0~10V(external load
resistor 2KΩ~1MΩ)
Digital input
range
-
-
10 bits Binary (0~1023)
Digital Output
Range
14 bits Binary (0~16383)
-1000~3500
-
Distinguish Ratio
1/16383(14Bit): The
converted data is stored
in PLC in Hex. (14Bit)
0.1
℃
1/1023(10Bit): The
converted data is stored
in PLC in Hex. (10Bit)
PID Output Value
0~K4095
-
Integral Precision
0.8%
±0.5
℃
0.8%
Convert Speed
20ms/CH
3ms/CH
Power Supply
DC24V±10%
,
100mA
Brief Introduction
1
Specification
2
3CH 14bits current input
、
4CH PT100 temperature input and 2CH 10bits voltage output
3CH AD is current (0~20mA
、
4~20mA) selectable; 2Ch DA is voltage (0~5V
、
0~10V)
selectable, choose via the software;
Pt resistor input, the scale is PT100
3CH A/D and 4CH PT input are equipped with PID auto tune function;
As the special module, 7pcs XC-E3AD4PT2DA can be connected to one XC series PLC main
unit;
Содержание XC Series
Страница 1: ...WUXI XINJE ELECTRIC CO LTD XC series PLC hardware User manual Data No PC01 20110106 3 3 ...
Страница 4: ......
Страница 41: ...3 System Structure Analog Output QD QD1000 QD1031 16 channels Module s Value D D8320 D8329 ...
Страница 43: ...3 System Structure Please install the products according to chapter 2 1 1 3 Installation Environment ...
Страница 49: ...5 Input Specifications and Wiring Methods 5 2 DC Input Signal AC Power Supply Type DC Input Signal 1 ...
Страница 51: ...5 Input Specifications and Wiring Methods ...
Страница 125: ...Appendix special soft device list 1 If you change special FLASH memory it will take into effect after restart the PLC ...