V5 series inverter
59
Fig.4-11 Starting mode 1
Fig. 4-12 Decelerate stop+DC brake
P2.05
Stopping mode
Range: 0,1,2
0
0: Decelerate stop
After receiving the stopping command, the inverter reduces its output frequency within decelerate time and stops when the
frequency becomes 0.
1: Free stop
After receiving the stopping command, the inverter stops immediately and the motor stops according to mechanical inertia.
2: Decelerate stop+DC brake
After receiving the stopping command, the inverter reduces its output frequency according to decelerate time and then start
to DC brake when reach P2.06 (stop brake starting frequency).
P2.06
Starting frequency of stop brake
Range: 0.0~15.00Hz
3.00Hz
P2.07
DC brake time when stopping
Range: 0.0~60.0s
0.0s
P2.08
DC brake current when stopping
Range: 0~80 (%)
0(%)
P2.08 is the percentage value of DC brake current and inverter rated current.There is no DC braking when the braking time
is 0.0, as shown in Fig.4-12.
4-2-4. Auxiliary running parameters (Group P3)
P3.00
Combination of frequency setting
channel
Range: 0~20
0