Group P0: Basic running parameters
Parameter
Name
Setting Range
Minmum
unit
Default setting
Change
P0.00
Control mode
selection
0: V/F control
1: open-loop vector control
1
0
×
P0.01
Frequency setting
mode
0: potentiometer on the panel
1: Increase/Decrease key
2: digital setting 1, via keys on the
panel
3: digital setting 2, via terminal
UP/DOWN
4: digit setting 3, via serial port
5: VI analog input (VI-GND)
6: CI analog input (CI-GND)
7: Pulse input (PULSE)
8: Combined setting mode (refer
to P3.00)
1
0
○
P0.02
Digital set the
running frequency
P0.19 max frequency ~ P0.20 min
frequency limit
0.01HZ
50.00HZ
○
P0.03
Running command
selection
0: operation panel
1: Teminal
2: serial port
1
0
○
P0.04
Running direction
setting
Lowest bit:
0: jog forward via panel
1: jog reverse via panel
Ten bit:
0: enable to reverse running
1: prohibit reverse running
1
00
○
P0.05
Run forward/reverse
dead zone time
0.0~120.0s
0.1s
0.1s
○
P0.06
Highest ouput
frequency
50.00Hz~500.00Hz
0.01Hz
50.00Hz
×
P0.07
Basic running
frequency
1.00Hz~500.00Hz
0.01Hz
50.00Hz
×
P0.08
Highest output
voltage
1~480V
1V
Inverter rated
voltage
×
P0.09
Torque boost
0.0%
~
30.0%
0.1%
2.0%
○
P0.10
Cut-off frequency
for torque boost
0.00Hz~basic running frequency
P0.07
0.00
25.00Hz
○
P0.11
Torque boost mode
0: manual
1: automatic
1
0
○
P0.12
Carrier frequency
1.0K~14.0K
0.1K
8.0K
×
P0.13
Acc/Dec mode
selection
0: linear Acc/Dec
1: S curve Acc/Dec
1
0
×
P0.14
Low speed time of
S curve
10.0%~50.0% (Acc/Dec time)
P0.14
+
P0.15
<
90%
0.1%
20.0%
○