V5 series inverter
47
9. Simple PLC operation parameters (Group P8)
Group P8: Simple PLC operation parameters
Parameters
Name
Range
Minmum
unit
Default
setting
Change
P8.00
Simple PLC operation
mode selection
0000~1113
Lowest bit: mode selection
0: Disabled
1: Stop after single cycle
2: keep the final value after single cycle
3: continuous cycle
Ten bit: PLC pause and restartup mode selection
0: Run again from stage 1
1: Continue running from the pause frequency
Hundred bit: save PLC parameter when power off
0: Not saving
1: Save the frequency when power off
Thousand bit: time unit of stage running
0: second
1: minute
1
0000
×
P8.01
Stage 1 setup
000~621
Lowest bit: frequency setup
0: Multi I (i
=
1~7)
1: Frequency P0.01
Ten bit: Operating direction selection
0: Run forward
1: Run reverse
2: Decided by operating instructions
Hundred bit: Acc/Dec time selection
0: Acc/Dec time 1
1: Acc/Dec time 2
2: Acc/Dec time 3
3: Acc/Dec time 4
4: Acc/Dec time 5
5: Acc/Dec time 6
6: Acc/Dec time 7
1
000
○
P8.02
Operating time of stage 1
0.1~6000.0
0.1
10.0
○
P8.03
Stage 2 setup
000~621
1
000
○
P8.04
Operating time of stage 2
0.1~6000.0
0.1
10.0
○
P8.05
Stage 3 setup
000~621
1
000
○
P8.06
Operating time of stage 3
0.1~6000.0
0.1
10.0
○
P8.07
Stage 4 setup
000~621
1
000
○
P8.08
Operating time of stage 4
0.1~6000.0
0.1
10.0
○
P8.09
Stage 5 setup
000~621
1
000
○
P8.10
Operating time of stage 5
0.1~6000.0
0.1
10.0
○
P8.11
Stage 6 setup
000~621
1
000
○
P8.12
Operating time of stage 6
0.1~6000.0
0.1
10.0
○
P8.13
Stage 7 setup
000~621
1
000
○
P8.14
Operating time of stage 7
0.1~6000.0
0.1
10.0
○