V5 series inverter
36
P0.15
Linear time of S
curve
10.0%~80.0%
(
Acc/Dec time
)
P0.14
+
P0.15
<
90%
0.1%
60.0%
○
P0.16
Acc/Dec time unit
0: second
1: minute
0
0
×
P0.17
Accerlate time 1
0.1~6000.0
0.1
10.0
○
P0.18
Decerlate time 1
0.1~6000.0
0.1
10.0
○
P0.19
High limit frequency
Lowest frequency ~highest output
frequency P0.06
0.01Hz
50.00Hz
×
P0.20
Low limit frequency
0.00Hz~highest frequency
0.01Hz
0.00Hz
×
P0.21
Running mode of
lowest frequency
0: running at lowest frequency
1: stop
1
0
×
P0.22
V/F curve setting
0: constant torque curve
1: torque-reducing curve 1 (1.2
powers)
2: torque-reducing curve 2 (1.7
powers)
3: torque-reducing curve 3 (2.0
powers)
4: multi-segment V/F curves
1
0
×
P0.23
V/F frequency value
P1
0.00~P0.25
0.01Hz
0.00Hz
×
P0.24
V/F voltage value
V1
0~ P0.26
0.1%
0.0%
×
P0.25
V/F frequency value
P2
P0.23 ~ P0.27
0.01Hz
0.00Hz
×
P0.26
V/F voltage value
V2
P0.24 ~ P0.28
0.1%
0.0%
×
P0.27
V/F frequency value
P3
P0.25 ~ P0.07 basic running
frequency
0.01Hz
0.00Hz
×
P0.28
V/F voltage value
V3
P0.26 ~ 100.0%
0.1%
0.0%
×
2. Frequency parameter (Group P1)
Group P1: reference frequency parameter
Parameter
Name
Setting range
Minmum
unit
Default setting
Change
P1.00
Time constant of
analog filter
0.01~30.00s
0.01s
0.20s
○
P1.01
The gain of VI
channel
0.01~9.99
0.01
1.00
○
P1.02
min setting value of
VI
0.00~P1.04
0.01V
0.00V
○
P1.03
Frequency of the
min setting of VI
0.00~highest frequency
0.01Hz
0.00Hz
○
P1.04
Max setting of VI
P1.04~10.00V
0.01V
10.00V
○
P1.05
Frequency of the
max setting of VI
0.00~highest frequency
0.01Hz
50.00Hz
○
P1.06
The gain of CI
channel
0.01~ 9.99
0.01
1.00
○
P1.07
Min setting of CI
0.00~ P1.09
0.01V
0.00V
○
P1.08
Frequency of the
min setting of CI
0.00~highest frequency
0.01Hz
0.00Hz
○