V5 series inverter
62
P3.09.
Lowest bit of LED:
Set baud rate, the values are shown below:
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
Ten bit of LED:
Set digital format, the values are show below:
0: 1
-
7
-
2 format, no parity check; 1 stop bit, 7 data bits, 2 stop bits, no parity.
1: 1
-
7
-
1 format, odd; 1 stop bit, 7 data bits, 1 stop bits, odd
2: 1
-
7
-
1 format, even; 1 stop bit, 7 data bits, 1 stop bit, even
3: 1
-
8
-
2 format, no parity check; 1 stop bit, 8 data bits, 2 stop bits, no parity.
4: 1
-
8
-
1 format, odd
;
1 stop bit, 8 data bits, 1 stop bit, odd
5: 1
-
8
-
1 format, even
;
1 stop bit, 8 data bits, 1 stop bit, even
6: 1
-
8
-
1 format, no parity check; 1 stop bit, 8 data bits, 1 stop bit, no parity.
Hundred bit of LED:
undefined
Note:
when choose
Modbus-RTU communication mode, you should select digital format 3~6.
P3.10
Inverter address
Range: 0~248
1
This parameter is used for identify the inverter’s address in serial communication.
0 is the broadcast address. If inverter is a slave, it doesn’t have to answer the 0 command.
248 is inverter host address. If set P3.10 to 248, it can send broadcast command to other inverters to realize multi-machine
working.
P3.11
Communicate overtime checking time
Range: 0.0~1000.0S
0.0s
When serial port communication failed and the lasting time is over this parameter, the inverter is considered as communi-
cation error.
When set the value to 0, the inverter will not detect the serial communication port and this function is disabled.
P3.12
Inverter response delay
Range: 0~1000ms
5ms
It refers to time from inverter’s serial port receiving and executing the command of host PC to returning response to it.
P3.13
Proportion of communication frequency
Range: 0.01~1.00
1.00
The real running frequency= the proportion * frequency command receiving from RS485 port.
This parameter can also set running frequency proportion of several inverters in multimachine linkage mode.
P3.14
Accerlate time 2
Range: 0.1~6000.0
10.0
P3.15
Decelerate time 2
Range: 0.1~6000.0
10.0
P3.16
Accerlate time 3
Range: 0.1~6000.0
10.0
P3.17
Decelerate time 3
Range: 0.1~6000.0
10.0
P3.18
Accerlate time 4
Range: 0.1~6000.0
10.0
P3.19
Decelerate time 4
Range: 0.1~6000.0
10.0
P3.20
Accerlate time 5
Range: 0.1~6000.0
10.0
P3.21
Decelerate time 5
Range: 0.1~6000.0
10.0
P3.22
Accerlate time 6
Range: 0.1~6000.0
10.0
P3.23
Decelerate time 6
Range: 0.1~6000.0
10.0
P3.24
Accerlate time 7
Range: 0.1~6000.0
10.0
P3.25
Decelerate time 7
Range: 0.1~6000.0
10.0