V5 series inverter
80
Fig. 4-43 PLC continuous running mode
3: Continuous cycle.
See Fig.4-43, inverter start next cycle after one cycle finished, it will stop when stop command is
input.
LED Ten bit: restart after pause
0: restart from stage 1.
Stop caused by stop command, fault or power-off, restart from the first stage.
1: Continue to run from the frequency of stopping stage.
Stop caused by stop command or fault, inverter auto-records
current stage running time. It will enter this stage after restarting and continue running, see Fig 4-44.
Fig.4-44 PLC start mode 1
Hundred bit
: PLC status parameter storage selection when power-off
0: Not save.
The inverter doesn’t save the PLC status. It restarts from stage 1 when power on.
1: Save.
The inverter saves the PLC status including stage frequency and running time when power-off. It restart according
to the running mode defined by LED ten bit(restart after pause).
Thousand bit:
the unit of PLC running time
0: second
1: minute
This unit is only valid for the definition of PLC running time. The unit of Acc/Dec time durning PLC is running is set by
P0.16.
Note:
(1) This stage is invalid when the PLC running time is set to 0.
(2) You can control pause, invalid, run and others of the PLC process via terminals, refer to P4 for details.
P8.01
Stage 1 setup
Range: 000~621
000
P8.02
Running time of stage1
Range: 0.1~6000.0
10.0
P8.03
Stage 2 setup
Range: 000~621
000
P8.04
Running time of stage 2
Range: 0.1~6000.0
10.0
P8.05
Stage 3 setup
Range: 000~621
000
P8.06
Running time of stage 3
Range: 0.1~6000.0
10.0