V5 series inverter
69
Fig. 4-23 3-wire operation mode 1
Xi is the multi-function input terminal of X1~X6; here you should define its function to No.9 “3-wire control mode”.
3: 3-wire control mode 2
SB1: Stop button
SB2: Running button
Fig.4-24 3-wire control mode 2
Xi is the multi-function input terminal of X1~X6, here you should define its function to No.9 “3-wire control mode”.
Note:
When the inverter alarming stop, if the running command channel is terminal and terminal FWD/REV is valid, in-
verter will reset the error and restart immediately.
P4.09
UP/DOWN speed rate
Range: 0.01~99.99Hz/s
1.00 Hz/s
This parameter defines the changing rate of setting frequency changed by UP/DOWN terminal.
P4.10
Bi-direction open-collector output terminal OC
Range: 0~20
0
P4.11
Relay output function selection
Range: 0~20
15
Bi-direction open-collector output terminal OC, the options of this parameter are shown in Table 4-6.
Table 4-6 Functions of output terminals
Setting
Functions
Setting
Functions
0
Inverter is running (RUN)
11
PLC one period running is completed
1
Frequency arriving signal (FAR)
12
Reach the setting counter value
2
Frequency level detection signal (FDT1)
13
Reach the middle counter value
3
Frequency level detection signal (FDT2)
14
Inverter running preparation finished (RDY)
4
Overload pre-alarm (OL)
15
Inverter fault
5
Inverter under voltage locking (LU)
16
Running at start frequency
6
External fault stop (EXT)
17
DC braking when startup