Woodward
Manual MRIK3-C EN
84
DOK-TD-MRIK3-C Rev. A
Protection parameter
LED Function
Unit
Default
Actual
settings
settings
Parameter set change-over switch
Set 1/2
Set
P2
Parameter set change-over switch
SET 1
1 2
I>
Pick-up value of the phase overcurrent element
x I
N
0.2
I>+CHAR Trip
characteristics for the phase overcurrent
element
DEFT
I>+t>
Tripping time (factor) for the phase overcurrent
element
(s) 0.03
I>+t>
Fast trip at manual switch on at I>
TIME
I>+CHAR+t>
Reset mode for the tripping characteristics
0s
I>>
Pick-up value for the phase short-circuit element
x I
N
0.50
I>>+CB green
Trip-Block for all protection elements
x I
N
EXIT
I>>+t>
Tripping time of the phase short-circuit element
s 0.03
I>>+t>
Fast trip at manual switch on at I>>
TIME
U
E
>**
Pick-up value of the residual voltage
V
1V/2V/5V
I
E
>
Pick-up value for earth overcurrent element
xIn(%)***
0.01(0.1)***
I
E
>
Warning/Tripping of the earth current stage
trip
I
E
>+t>+
green**
Tripping time in forward direction
s
0,04
I
E
>+t>+
red**
Tripping time in reverse direction
s
0.04
I
E
>+t>*
Tripping delay time for earth overcurrent element
s
0.04
I
E
>+t>
Fast trip at manual switch on at I
E
>
TIME
I
E
>>
Pick-up value for the earth short-circuit element
xIn(%)*** 0.01(0.1)***
IE>>+t>+
green** Tripping time in forward direction
s
0.04
IE>>+t>+
red**
Tripping time in reverse direction
s
0.04
IE>>+t>*
Tripping delay time for earth short circuit element
s
0.04
I
E
>>+t>
Fast trip at manual switch on at I
E
>>
TIME
I
E
>+I
E
>>**
Switch over for SIN/COS
SIN
* LED-Display at MRIK3-ICE relay type
** LED display at MRIK3-ICER, MRIK3-ICXR relay types
()*** Setting at MRIK3-ICXR relay type
AR Parameter
LED Function
Unit
Default
Actual
settings
settings
Parameter set change-over switch
Set 1/2
1
2
SHOT
Number of Shots
4
t
F
Fault time t
F
s
0.10
t
D1
Dead time t
D1
s
1.00
t
D2
Dead time t
D2
s
2.00
t
D3
Dead time t
D3
s
2.00
t
D4
Dead time t
D4
s
2.00
t
CI
Close impulse time t
CI
s
0.50
t
R
Reclaim time t
R
s
10.0
t
f
+ I>+I>>+I
E
>+
I
E
>> green
Fault time activation t
F
1ST
Control functions
LED Function
Unit
Default
Actual
settings
settings