Close
impulse time (tCI)
During close impulse time t
CI
the NO C.B. contact of MRIK3-C is closed. It starts with expiration of
the dead time and is interrupted earlier when the ON-signal of the circuit breaker is already present
before expiration of the time.
6.6.5
Reclaim time (tR)
This is the time during which - after switching on (also manually) or after AR - a subsequent reclos-
ing is prevented. If the number of the set shots is reached, the MRIK3-C is blocked for this time af-
ter the last reclosing attempt.
The reclaim time is started with the automatic closing command or by switching on manually. An
OFF-command which occurs after the last permissible AR leads to a final switching-off.
6.6.6
Fault
time
activation
This parameter can be used to fix whether the supervision of the fault time is active for the first trip-
ping action or for all tripping actions (see 6.6.2)