7.3
Secondary injection test
7.3.1
Test
equipment
Voltmeter, Ammeter with class 1 or better,
auxiliary power supply with the voltage corresponding to the rated data on the type plate,
single-phase current supply unit (adjustable from 0 to
4 x In),
single-phase voltage supply unit (adjustable from 0 to
1.2 x Un) (Only for relays with direc-
tional feature),
timer to measure the operating time (Accuracy class
10 ms),
switching device and
test leads and tools.