Woodward
Manual MRIK3-C EN
52
DOK-TD-MRIK3-C Rev. A
6.11
Setting of the clock
When date and time are set, the LED „
“ is on. The following method is used:
Date: year
Y=00
month
M=00
day
D=00
time: hour
h=00
minute
m=00
second
s=00
Immediately when the supply voltage is applied the clock starts with the respective date and time.
The time is buffered against short-term voltage failures (min. 6 minutes).
Note:
The window for setting the clock is behind the measuring value reading. Access to the window is
given via push-button <SELECT/RESET>.
6.12
Additional functions
6.12.1
Blocking the protection functions
Blocking of the protective functions:
The MRIK3-C
is equipped with a blocking function that can be parameterized arbitrary. Connecting
supply voltage to terminals at a assigned digital blocking of those functions which were selected by
the user takes place.
It is possible to choose between two types of protective blocking:
1) Blocking of the individual protection stages. The excitation of the blocked protection stage is
blocked..
2) Blocking of the individual tripping stages. The individual protection stages are excited and the
set tripping time expires. Tripping only takes place when:
a) the voltage at the blocking input is reduced;
b) the voltage at the blocking input is applied, the tripping time and the blocking time have ex-
pired. (refer to chapter 6.7.1)
Parameter setting is to be carried out as follows:
After the <ENTER> and <TRIP> keys have been actuated simultaneously, the display
shows the text "PR_B" (the protection stages are blocked) or "TR_B" (the tripping stages
are blocked).
The settings can be changed by actuating the keys <+> or <->. In this procedure, the LEDs
I>; I>>; IE>; IE>> are simultaneously alight in case of protective blocking "PR_B" and LEDs
tI>; tI>>; tIE>, tIE>> simultaneously emit light in case of trip blocking "TR_B".
Actuation of the <ENTER> key with a one-time entry of the password will store the set
function.
After this actuate the <SELECT/RESET> key to call up the first blockable protection func-
tion.
The display will show the text "BLOC" (the respective function is blocked) or "NO_B" (the
respective function is not blocked.
Actuation of the <ENTER> key will store the set function.
By pressing the <SELECT/RESET> pushbutton, all further protective function that can be
blocked are called one after the other.
After selection of the last blocking function renewed pressing of the <SELECT/RESET> pushbutton
switches to the assignment mode of the output relays.