Manual MRIK3-C EN
Woodward
DOK-TD-MRIK3-C Rev. A
47
6.7
Control
functions
6.7.1
Block/Trip-time
The block/trip serves for recognising a CB failure protection by rear interlocking. Setting of the
blocking input will activate the blocking function and block the configured protection functions. (re-
fer to chapter 5.11.1) If the block/trip time is not set to EXIT but to an adjustable time (0.1 – 2.00s),
the blocking function is cancelled again after this time has expired. If trip blocking was set to pro-
tection blocking PR_B, protection excitation with subsequent tripping will take place after expiration
of the set time when blocking is cancelled on expiration of the block/trip time. If blocking is set to
trip blocking TR_B, there will be immediate tripping after blocking has been cancelled following ex-
piration of the block/trip time if the set time of the responding protection step has already expired.
Figure 6.3:
6.7.2
Time delay for ext. Trip
Via a digital input a external trip with settable time is settable. The trip take place by the means of o
high voltage level at the input for the set time. It is possible to assign this in out function to the out-
put relay. Also it can assign to the alarm relay.
6.7.3
Dead time for Trip/Restore
This function fulfils the requirements for a manual switch ON operation. When a high level at the
assigned digital input take place, the relay trips immediately. When the digital input is reset to low
level a counter starts and after the selectable delay time (0,1s – 300s) the relay switch ON the CB.
Figure 6.4:
I>
+
+
+
tI>
tI>
t
1
0
I>
Block/
Trip time
t
1
0
Protection Block
Trip
Block
t
1
0