Woodward
Manual MRIK3-C EN
74
DOK-TD-MRIK3-C Rev. A
8.3.2
Time
overcurrent protection (I-type)
Setting
range Step
Tolerance
I>
t
I>
0.2...4.0 x I
N
(EXIT)
0.03 - 300 s (EXIT)
(definite time)
0.05 - 10 (EXIT)
(inverse time)
0.01; 0.02; 0.05; 0.1 x I
N
0.01; 0.02; 0.05; 0.1; 0.2; 0.5;
1.0; 2.0; 5.0; 10 s; 20 s
0.01; 0.02; 0.05; 0.1; 0.2
3% of the setting value or
min.
2 % In
3% or
10 ms
3% of the measuring value
of the current or
20ms (see
EN60255-3)
I>>
t
I>>
0,5...40 x I
N
(EXIT)
0,03...10 s (EXIT)
0.02; 0.05; 0.1; 0.2; 0.5; 1.0 x I
N
0.01 s; 0.02 s; 0.05 s; 0.1 s; 0.2 s
3% of the setting value or
min.
2% In
3% or
10 ms
I>>+CB
Trip/
Block
0,5...40 x I
N
(EXIT)
0.02; 0.05; 0.1; 0.2; 0.5; 1.0 x I
N
3% of the setting value or
min.
2% In
8.3.3
Earth fault protection (E - type)
Setting
range Step
Tolerance
I
E>
t
IE>
0.01...2.0 x I
N
(EXIT)(E)
0.03...300 s (EXIT)
(definite time)
0.05...10 (EXIT)
(inverse time)
0.001; 0.002; 0.005; 0.01; 0.02;
0.05 x I
N
0.01; 0.02; 0.05; 0.1; 0.2; 0.5;
1.0; 2.0; 5.0; 10; 20 s
0.01; 0.02; 0.05; 0.1; 0.2
5% of the setting value or
0,3% I
N
(E);
3% or 15 ms
3% of the measuring value
of the current or
20ms (see
EN60255-4)
I
E>>
t
IE>>
0.01...15,0 x I
N
(EXIT)(E)
0.040...10 s (EXIT)
0.001; 0.002; 0.005, 0.01; 0.02;
0.05; 0.1; 0.2; 0.5 x I
N
0.01; 0.02; 0.05 s; 0.1 s; 0.2 s
5% of the setting value or
0.3% I
N
(E);
3% or
15 ms
8.3.4
Earth fault protection (ER/XR-type)
Setting
range Step
Tolerance
I
E>
t
IE>
0.01...0.45 x I
N
(EXIT) (ER)
0.1... 5.0% I
N
(EXIT)
(XR)
0.04…300s (EXIT)
0.001; 0.002; 0.005; 0.01 x I
N
0.01%; 0.02%; 0.05%; 0.1% I
N
0.01; 0.02; 0.05; 0.1; 0.2; 0.5;
1.0; 2.0; 5.0; 10; 20 s
5% of the setting value or
0.3% I
N
(ER);
0.03% I
N
(XR)
3% or
15 ms
I
E>>
t
IE>>
0.01...0.45 x I
N
(EXIT) (ER)
0.1...5.0% I
N
(EXIT)
(XR)
0.04...10 s (EXIT)
0.001; 0.002; 0.005; 0.01 x I
N
0.01%; 0.02%; 0.05%; 0.1% I
N
0.01; 0.02; 0.05 s; 0.1 s; 0.2 s
5% of the setting value or
0.3% I
N
(ER);
0.03% I
N
(XR)
3% or
15 ms