7.4.6
Checking the auto reclosing function
The auto reclosing function can only be tested by means of an auxiliary relay simulating the C.B.
and a push button for manual start. In order to simplify testing, the significant settings of the de-
vices and the value of the test current are provided as follows:
I>
= 0,8 x I
N
I> +CHAR
= DEFT
tI>
= 2 s
I>>
= 1,2 x I
N
tI>>
= 0,5 s
SHOT
= 1
tF =
1,5
tD1
= 5 s
tD2
= 10 s
tCI
= 0,2 s
tR
= 10 s
tF + I>,I>>(IE>,IE>>)
= 1ST
CB (tCBFP)
= 2 s (EXIT)
f
N
= 50 Hz or 60 Hz
Relay assignment:
refer to default settings
AR-assignment:
I> =
YES
I>>
=
YES
The test circuit must be set up in accordance with Figure 7.1. First the push button is pressed. The
auxiliary relay picks up and the LED CB lights up. With the settings of the devices as shown above,
a test current of 1.5 x I
N
should be injected on phase L1. When the pickup value is exceeded, trip-
ping takes place at once and the LEDs I>> and L1 light up red.
The auxiliary relay releases again. The device changes into the "Starting" status. Now the dead
time is running and the LED tD1 lights up green. After expiration of the dead time the LED tCI
briefly lights up and the auxiliary relay trips again.
The display shows "CLOS". The LED tR lights up red. The LED tR signals that the reclaim time is
running. Once it has expired, all LEDs extinguish except for the LED CB, and the display shows
"MRIK" again. This completes a successful AR simulation.
Note:
After the relay has tripped, the test current should be switched off as quickly as possible. Other-
wise, there is the danger that the switch failure protection device CBFP picks up. If switching off
quickly is impossible, tCBFP must be set to "EXIT".
7.4.7
Checking the circuit breaker position
First the digital inputs have to be assigned the relevant functions. In order to recognised the circuit
breaker position, at least the CB position ON or the CB position OFF must be configured. The cor-
rect display of the CB LED can be found in chapter 5.7.10.
Behaviour with AR function
If the circuit breaker is set to position ON, the LED tR will light up for the duration of the set block-
ing time and the display shows "MANU". The CB LED shows a red light.
Behaviour without AR function
If the circuit breaker is set to position ON, the light of the CB LED will be red.