Manual MRIK3-C EN
Woodward
DOK-TD-MRIK3-C Rev. A
53
Function Display LED/Colour
Blocking of the protection
stage
PR_B
I>; I>>; I
E
>;
I
E
>>
Blocking of the trip func-
tion
TR_B t
I
>; t
I
>>; t
IE
>;
t
IE
>>
I> Overcurrent
NO_B
I>
green
I>>
Short circuit
BLOC I>> green
I
E>
Earth current
1
st
element
NO_B I
E>
green
I
E>>
Earth
current
2
nd
element
NO_B I
E>>
green
t
CBFP
Circuit
breaker
failure protec-
tion
NO_B CB
green
DI+Trip Ext.
tripping
NO_B DI+Trip
Table 6.3: Default settings of both parameter sets
6.12.2
Assignment of the output relays
Unit MRI3 has five output relays. The fifth output relay is provided as permanent alarm relay for self
supervision is normally on. Output relays 1 - 4 are normally off and can be assigned as alarm or
tripping relays to the current functions which can either be done by using the push buttons on the
front plate or via serial interface RS485. The assignment of the output relays is similar to the setting
of parameters, however, only in the assignment mode. The assignment mode can be reached only
via the blocking mode.
By pressing push button <SELECT/RESET> in blocking mode again, the assignment mode is se-
lected.
The relays are assigned as follows: LEDs I>, I>>, I
E
>, I
E
>> are two-coloured and light up
green
when the output relays are assigned as
alarm relays
and
red
as
tripping relays
. In case of the
MRIK3-C models the LEDs I>; I>>; I
E
> and I
E
>> always light up in conjunction with t>.
In addition, the LED
also lights up with each adjustment. Green means forward and red back-
ward direction.
Definition:
Alarm relays are activated at pickup.
Tripping relays are only activated after elapse of the tripping delay.
The adjustment procedure is as follows:
Allocation of one or more of the 4 output relays
to “Alarm” or “Trip” of each of the protective functions. Which of the function is just being processed
is signalled by the LEDs. (see Table 6.4 and Table 6.5)
Indica-
tion
LED Allocated
relay(s)
_ _ _ _
None
1 _ _ _
1
_ 2 _ _
2
...
...
_ 2 3 4
2, 3 and 4
1 2 3 4
all
By pressing push-buttons <+> and <-> all possible combinations can be realised. The selected al-
location can be saved by <ENTER> and subsequent entry of the password.