5.4.12 The unit is programmed for two shots, unsuccessful AR
Figure 5.2: Two shots, AR unsuccessful
Here the time sequence as described in para.5.4.11. The second reclosing shot is however unsuc-
cessful.
5.4.13 Manual closing of the circuit breaker to faulty lines
Figure 5.3: Manual closing of the C.B. to faulty lines
Unit MRIK3-C is in "inactive" status when the circuit breaker is switched off. When the C.B. is
manually closed the reclaim time is started. In case there is a faulty line the C.B. is switched off by
mains protection of the relay. After elapse of the reclaim time unit MRIK3-C changes over to "inac-
tive" status.
Short
circuit
Protection
energized
Protection
tripped
Circuit breaker
Switch on
command
Manual on
Protection tripped