Manual 37135C
IKD 1 - Digital I/O Expansion Board
Page 26/41
© Woodward
Remote acknowledg
[x = 1 to 8]
Select input for acknowledgment
YES/NO
Any of the discrete inputs can be set as the acknowledgment input. If a acknowledg-
ment input is set all triggering are reset if the input signal is reset for at least the con-
figured reset delay of each input. If a triggering delay is configured for the acknowl-
edgment input this time has to be over until a acknowledgment is accepted.
NO
................ The input is no acknowledgment input. (for operation with GCP)
YES
.............. The input is an acknowledgment input.
Note:
If an input is configured as an acknowledgment input he also should be configured to
self acknowledgment and alarm class "control input".