1128600
SmartPAC 2 with WPC 2000 Integration User Manual
6-48
Run Mode
Single-stroke, Foot Operation
Single-stroke, Foot operation can only be used with WPC 2000 systems running Two-hand/
One-hand/Foot firmware and employing a Shadow light curtain to guard the point of
operation.
Two modes are available when you run the press in Single-stroke Foot. In Foot Trip mode,
you can initiate a complete stroke by simply pressing and releasing the Foot Switch. In Foot
Control mode, you must press and hold the Foot Switch through the Auto Carry-up Angle to
complete a stroke. You select the mode by setting option switch 3 on the Press Control
Option Switch Menu (see step 1, below).
To run the press in Single-stroke, Foot mode, do the following:
1.
Set option switch 3 on the Press Control Option Switch Menu to OPEN to operate the
press in Foot Trip mode (see
Enabling Foot Control in a Foot Switch
switch 3 to CLOSED to operate in Foot Control mode.
2.
With “FOOT” highlighted on the Mode Select Menu, depress the Foot Switch to initiate a
stroke, releasing or holding the pedal depending on the option switch 3 setting.
•
Release the Foot Switch if option switch 3 is set for Foot Trip
•
Hold the Foot Switch through the Auto Carry-up Angle if option switch 3 is set for Foot
Control
The ram completes the stroke, coming to rest at Top-stop.
INCORRECT INSTALLATION
You must install a Shadow light curtain correctly and connect it to WPC 2000 properly in order to
run the press in Single-stroke, Foot mode.
Failure to comply with these instructions will result in death or serious injury.
INTERRUPTED STROKE
In Foot Control mode, if you remove your foot from the Foot Switch before the ram
reaches the Auto Carry-up Angle, the press will stop, the “Interrupted Stroke” message will
flash on the SmartPAC 2 display, and WPC 2000 will switch to Two-hand Maintained
Single-stroke mode for the remainder of the stroke. To clear the “Interrupted Stroke”
message and return to Single-stroke, Foot operation, press both Run/Inch palm buttons
on the Operator Station and hold them until the press returns to Top-stop.
DANGER
!
NOTICE
Содержание SmartPAC 2
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 28: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual xxii Table of Contents ...
Страница 44: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual 1 16 Introduction ...
Страница 186: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual 3 26 Keyboard Displays Etc ...
Страница 440: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual D 12 Updating SmartPAC 2 Firmware ...
Страница 478: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual G 6 Replacing SmartPAC 2 PC Board ...
Страница 548: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual GL 8 Glossary ...
Страница 558: ...1128600 SmartPAC 2 with WPC 2000 Integration User Manual IN 10 Index ...
Страница 560: ......
Страница 562: ......
Страница 564: ......
Страница 566: ......
Страница 568: ......
Страница 570: ......
Страница 572: ......
Страница 574: ......
Страница 576: ......
Страница 577: ......
Страница 578: ...APPROVALS SCALE C SIZE TITLE SHEET OF DRAWING NUMBER REV ...
Страница 579: ...APPROVALS SCALE C SIZE TITLE SHEET OF DRAWING NUMBER REV ...
Страница 580: ...APPROVALS SCALE C SIZE TITLE SHEET OF DRAWING NUMBER REV ...
Страница 581: ...APPROVALS SCALE C SIZE TITLE SHEET OF DRAWING NUMBER REV ...
Страница 582: ......
Страница 583: ......
Страница 584: ......
Страница 585: ......
Страница 586: ......
Страница 587: ......
Страница 588: ......
Страница 589: ......
Страница 590: ......
Страница 591: ......
Страница 592: ......
Страница 593: ......
Страница 594: ......
Страница 595: ......
Страница 596: ......
Страница 597: ......
Страница 598: ......
Страница 599: ......
Страница 600: ......
Страница 601: ......
Страница 602: ......
Страница 603: ......
Страница 604: ......