Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 162
PID Set 4 - Overlap/Deadband
PID Set 4 - Overlap/Deadband For Loop 2
Dec
4461
20845 41690
RW
PID Set 4 overlap (+ve) or deadband (-ve) between primary &
secondary prop bands. In display units - limited to 20% of the
combined band width.
Hex
116D
516D
A2DA
PID Set 4 - On/Off Differential
PID Set 4 - On/Off Differential For Loop 2
Dec
4480
20864 41728
RW
The on-off control hysteresis (deadband) for PID Set 4.
1 to 300 display units, centred about the setpoint.
Hex
1180
5180
A300
PID Set 5 - Primary Prop Band
PID Set 5 Primary Proportional Band For Loop 2
Dec
4462
20846 41692
RW
Primary Proportional Band for Gain Set 5.
1 display unit to 9999 units,
but limited to 10 x scaled input span. 0 = On-Off control
Hex
116E
516E
A2DC
PID Set 5 - Secondary Prop Band
PID Set 5 Secondary Proportional Band For Loop 2
Dec
4463
20847 41694
RW
Secondary Proportional Band for Gain Set 5.
1 display unit to 9999 units,
but limited to 10 x scaled input span. 0 = On-Off control
Hex
116F
516F
A2DE
PID Set 5 - Integral Time
PID Set 5 - Integral Time For Loop 2
Dec
4464
20848 41696
RW
Gain Set 5 integral time constant for Loop 2
0.1 to 5999 Seconds. 0 or 6000 = OFF
Hex
1170
5170
A2E0
PID Set 5 - Derivative Time
PID Set 5 - Derivative Time For Loop 2
Dec
4465
20849 41698
RW
Gain Set 5 derivative time constant for Loop 2
0.1 to 5999 Seconds. 0 or 6000 = OFF
Hex
1171
5171
A2E2
PID Set 5 - Overlap/Deadband
PID Set 5 - Overlap/Deadband For Loop 2
Dec
4466
20850 41700
RW
PID Set 5 overlap (+ve) or deadband (-ve) between primary &
secondary prop bands. In display units - limited to 20% of the
combined band width.
Hex
1172
5172
A2E4
PID Set 5 - On/Off Differential
PID Set 5 - On/Off Differential For Loop 2
Dec
4481
20865 41730
RW
The on-off control hysteresis (deadband) for PID Set 5.
1 to 300 display units, centred about the setpoint.
Hex
1181
5181
A302
Loop 2 Gain Set 2 Breakpoint
Gain Scheduling PID Set 1 To 2 Switch Point
Dec
4469
20853 41706
RW
Value (SP or PV) gain scheduling switches from PID Set 1 to 2.
Value between Scaled Input 2 Lower & Upper Limits
Hex
1175
5175
A2EA
Loop 2 Gain Set 3 Breakpoint
Gain Scheduling PID Set 2 To 3 Switch Point
Dec
4470
20854 41708
RW
Value (SP or PV) gain scheduling switches from PID Set 2 to 3.
Value between Set 2 Breakpoint & Scaled Input 2 Upper Limit.
Hex
1176
5176
A2EC
Loop 2 Gain Set 4 Breakpoint
Gain Scheduling PID Set 3 To 4 Switch Point
Dec
4471
20855 41710
RW
Value (SP or PV) gain scheduling switches from PID Set 3 to 4.
Value between Set 3 Breakpoint & Scaled Input 2 Upper Limit.
Hex
1177
5177
A2EE
Loop 2 Gain Set 5 Breakpoint
Gain Scheduling PID Set 4 To 5 Switch Point
Dec
4472
20856 41712
RW
Value (SP or PV) gain scheduling switches from PID Set 4 to 5.
Value between Set 4 Breakpoint & Scaled Input 2 Upper Limit.
Hex
1178
5178
A2F0
Slave Setpoint Scale Minimum
0% Master Power Demand to Slave Setpoint Scaling
Dec
4485
20869 41738
RW
The effective cascade slave setpoint value equating to 0% power
demand from the master loop.
Hex
1185
5185
A30A
Slave Setpoint Scale Maximum
100% Master Power Demand to Slave Setpoint Scaling
Dec
4486
20870 41740
RW
The effective cascade slave setpoint value equating to 100%
power demand from the master loop.
Hex
1186
5186
A30C
Slave Setpoint
Slave Setpoint Value for Cascade Control
Dec
4492
20876 41752
RW
The slave setpoint valve when in Cascade Control Mode.
Only write to this parameter if the unit is cascade status is OPEN
(e.g. when tuning slave).
Hex 118C
518C
A318