Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 156
PID Set 3 - On/Off Differential
PID Set 3 - On/Off Differential For Loop 1
Dec
4379
20763 41526
RW
The on-off control hysteresis (deadband) for PID Set 3.
1 to 300 display units, centred about the setpoint.
Hex
111B
511B
A236
PID Set 4 - Primary Prop Band
PID Set 4 Primary Proportional Band For Loop 1
Dec
4357
20741 41482
RW
Primary Proportional Band for Gain Set 4.
1 display unit to 9999 units,
but limited to 10 x scaled input span. 0 = On-Off control
Hex
1105
5105
A20A
PID Set 4 - Secondary Prop Band
PID Set 4 Secondary Proportional Band For Loop 1
Dec
4358
20742 41484
RW
Secondary Proportional Band for Gain Set 4.
1 display unit to 9999 units,
but limited to 10 x scaled input span. 0 = On-Off control
Hex
1106
5106
A20C
PID Set 4 - Integral Time
PID Set 4 - Integral Time For Loop 1
Dec
4359
20743 41486
RW
Gain Set 4 integral time constant for loop 1
0.1 to 5999 Seconds. 0 or 6000 = OFF
Hex
1107
5107
A20E
PID Set 4 - Derivative Time
PID Set 4 - Derivative Time For Loop 1
Dec
4360
20744 41488
RW
Gain Set 4 derivative time constant for loop 1
0.1 to 5999 Seconds. 0 or 6000 = OFF
Hex
1108
5108
A210
PID Set 4 - Overlap/Deadband
PID Set 4 - Overlap/Deadband For Loop 1
Dec
4361
20745 41490
RW
PID Set 4 overlap (+ve) or deadband (-ve) between primary &
secondary prop bands. In display units - limited to 20% of the
combined band width.
Hex
1109
5109
A212
PID Set 4 - On/Off Differential
PID Set 4 - On/Off Differential For Loop 1
Dec
4380
20764 41528
RW
The on-off control hysteresis (deadband) for PID Set 4.
1 to 300 display units, centred about the setpoint.
Hex
111C
511C
A238
PID Set 5 - Primary Prop Band
PID Set 5 Primary Proportional Band For Loop 1
Dec
4362
20746 41492
RW
Primary Proportional Band for Gain Set 5.
1 display unit to 9999 units,
but limited to 10 x scaled input span. 0 = On-Off control
Hex
110A
510A
A214
PID Set 5 - Secondary Prop Band
PID Set 5 Secondary Proportional Band For Loop 1
Dec
4363
20747 41494
RW
Secondary Proportional Band for Gain Set 5.
1 display unit to 9999 units,
but limited to 10 x scaled input span. 0 = On-Off control
Hex
110B
510B
A216
PID Set 5 - Integral Time
PID Set 5 - Integral Time For Loop 1
Dec
4364
20748 41496
RW
Gain Set 5 integral time constant for loop 1
0.1 to 5999 Seconds. 0 or 6000 = OFF
Hex
110C
510C
A218
PID Set 5 - Derivative Time
PID Set 5 - Derivative Time For Loop 1
Dec
4365
20749 41498
RW
Gain Set 5 derivative time constant for loop 1
0.1 to 5999 Seconds. 0 or 6000 = OFF
Hex
110D
510D
A21A
PID Set 5 - Overlap/Deadband
PID Set 5 - Overlap/Deadband For Loop 1
Dec
4366
20750 41500
RW
PID Set 5 overlap (+ve) or deadband (-ve) between primary &
secondary prop bands. In display units - limited to 20% of the
combined band width.
Hex
110E
510E
A21C
PID Set 5 - Overlap/Deadband
PID Set 5 - On/Off Differential For Loop 1
Dec
4381
20765 41530
RW
The on-off control hysteresis (deadband) for PID Set 5.
1 to 300 display units, centred about the setpoint.
Hex
111D
511D
A23A
Loop 1 Gain Set 2 Breakpoint
Gain Scheduling PID Set 1 To 2 Switch Point
Dec
4369
20753 41506
RW
Value (SP or PV) gain scheduling switches from PID Set 1 To 2.
Value between Scaled Input 1 Lower & Upper Limits
Hex
1111
5111
A222
Loop 1 Gain Set 3 Breakpoint
Gain Scheduling PID Set 2 To 3 Switch Point
Dec
4370
20754 41508
RW
Value (SP or PV) gain scheduling switches from PID Set 2 To 3.
Value between Set 2 Breakpoint & Scaled Input 1 Upper Limit.
Hex
1112
5112
A224