Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 116
Input 1 Multi-point Scaling Enable
Value
Multi-point Scaling Status
Dec
1053
17437 34874
RW
0
Disabled
Hex
041D
441D
883A
1
Enabled (
valid only if the input type is linear
)
Input 1 Scale Point 1
Multi-Point Scaling Point 1
Dec
1054
17438 34876
RW
Percentage of the scaled input where multi-point scaling value 1
is applied.
0.1 to 100.0% *set to 100% ends scaling sequence at that point.
Hex
041E
441E
883C
Input 1 Display Point 1
Multi-Point Scaling Display Value For Point 1
Dec
1055
17439 34878
RW
Value to display at multi-point scaling point 1
Valid between the scaled input lower & upper limits
Hex
041F
441F
883E
Input 1 Scale Point 2
Multi-Point Scaling Point 2
Dec
1056
17440 34880
RW
Percentage of the scaled input where multi-point scaling value 2
is applied.
0.1 to 100.0% *set to 100% ends scaling sequence at that point.
Hex
0420
4420
8840
Input 1 Display Point 2
Multi-Point Scaling Display Value For Point 2
Dec
1057
17441 34882
RW
Value to display at multi-point scaling point 2
Valid between the scaled input lower & upper limits
Hex
0421
4421
8842
Input 1 Scale Point 3
Multi-Point Scaling Point 3
Dec
1058
17442 34884
RW
Percentage of the scaled input where multi-point scaling value 3
is applied.
0.1 to 100.0% *set to 100% ends scaling sequence at that point.
Hex
0422
4422
8844
Input 1 Display Point 3
Multi-Point Scaling Display Value For Point 3
Dec
1059
17443 34886
RW
Value to display at multi-point scaling point 3
Valid between the scaled input lower & upper limits
Hex
0423
4423
8846
Input 1 Scale Point 4
Multi-Point Scaling Point 4
Dec
1060
17444 34888
RW
Percentage of the scaled input where multi-point scaling value 4
is applied.
0.1 to 100.0% *set to 100% ends scaling sequence at that point.
Hex
0424
4424
8848
Input 1 Display Point 4
Multi-Point Scaling Display Value For Point 4
Dec
1061
17445 34890
RW
Value to display at multi-point scaling point 4
Valid between the scaled input lower & upper limits
Hex
0425
4425
884A
Input 1 Scale Point 5
Multi-Point Scaling Point 5
Dec
1062
17446 34892
RW
Percentage of the scaled input where multi-point scaling value 5
is applied.
0.1 to 100.0% *set to 100% ends scaling sequence at that point.
Hex
0426
4426
884C
Input 1 Display Point 5
Multi-Point Scaling Display Value For Point 5
Dec
1063
17447 34894
RW
Value to display at multi-point scaling point 5
Valid between the scaled input lower & upper limits
Hex
0427
4427
884E
Input 1 Scale Point 6
Multi-Point Scaling Point 6
Dec
1064
17448 34896
RW
Percentage of the scaled input where multi-point scaling value 6
is applied.
0.1 to 100.0% *set to 100% ends scaling sequence at that point.
Hex
0428
4428
8850
Input 1 Display Point 6
Multi-Point Scaling Display Value For Point 6
Dec
1065
17449 34898
RW
Value to display at multi-point scaling point 6
Valid between the scaled input lower & upper limits
Hex
0429
4429
8852
Input 1 Scale Point 7
Multi-Point Scaling Point 7
Dec
1066
17450 34900
RW
Percentage of the scaled input where multi-point scaling value 7
is applied.
0.1 to 100.0% *set to 100% ends scaling sequence at that point.
Hex
042A
442A
8854
Input 1 Display Point 7
Multi-Point Scaling Display Value For Point 7
Dec
1067
17451 34902
RW
Value to display at multi-point scaling point 7
Valid between the scaled input lower & upper limits
Hex
042B
442B
8856
Содержание Pro-EC44
Страница 1: ...Pro EC44 2 Loop Graphical Profile Controller Recorder Pro EC44 User Guide 59540 2 ...
Страница 2: ......
Страница 6: ......