Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 172
Memory Remaining
Remaining Data Recorder Capacity
Dec
7554
23938 47876
RO
The unused memory remaining, in bytes.
Hex
1D82
5D82
BB04
Time Remaining
Remaining Data Recorder Time
Dec
7555
23939 47878
RO
Approximate recording time remaining until memory filled, in
seconds. Based on the current recorder settings & sample rate.
Hex
1D83
5D83
BB06
Recorder Auto-Alarm Trigger
Value
Automatic Data Recorder Trigger
Dec
7563
23947 47894
RW
0
None
Hex
1D8B
5D8B
BB16
1
On Alarm
2
On Profile Run
3
On Alarm or Profile Running
Operator Access To Record Trigger
Value
Operator Access To Manual Record Trigger
Dec
7559
23943 47886
RW
0
No
Hex
1D87
5D87
BB0E
1
Yes
Recorder Status In Operator Mode
Value
Recorder Status Visible In Operator Mode
Dec
7560
23944 47888
RW
0
No
Hex
1D88
5D88
BB10
1
Yes
Record Input 1 Process Variable
Value
Record Process Variable Of Input 1
Dec
7572
23956 47912
RW
0
Do Not Record PV
Hex
1D94
5D94
BB28
1
Record PV Value
Record Input 1 Max Between Samples
Value
Record Max PV For Input 1 Since Last Sample
Dec
7573
23957 47914
RW
0
Do Not Record Maximum PV
Hex
1D95
5D95
BB2A
1
Record Maximum PV Between Samples
Record Input 1 Min Between Samples
Value
Record Min PV For Input 1 Since Last Sample
Dec
7574
23958 47916
RW
0
Do Not Record Minimum PV
Hex
1D96
5D96
BB2C
1
Record Minimum PV Between Samples
Record Input 2 Process Variable
Value
Record Process Variable Of Input 2
Dec
7607
23991 47982
RW
0
Do Not Record PV
Hex
1DB7
5DB7
BB6E
1
Record PV Value
Record Input 2 Max Between Samples
Value
Record Max PV For Input 2 Since Last Sample
Dec
7608
23992 47984
RW
0
Do Not Record Maximum PV
Hex
1DB8
5DB8
BB70
1
Record Maximum PV Between Samples
Record Input 2 Min Between Samples
Value
Record Min PV For Input 2 Since Last Sample
Dec
7609
23993 47986
RW
0
Do Not Record Minimum PV
Hex
1DB9
5DB9
BB72
1
Record Minimum PV Between Samples
Record Aux A Input
Value
Record Auxiliary A Input Value
Dec
7606
23990 47980
RW
0
Do Not Record Aux A
Hex
1DB6
5DB6
BB6C
1
Record Aux A Value
Record Loop 1 Actual Setpoint
Value
Record Effective Value of Loop 1 Setpoint
Dec
7575
23959 47918
RW
0
Do Not Record Setpoint
Hex
1D97
5D97
BB2E
1
Record Actual Setpoint
Record Loop 2 Actual Setpoint
Value
Record Effective Value of Loop 2 Setpoint
Dec
7610
23994 47988
RW
0
Do Not Record Setpoint
Hex
1DBA
5DBA
BB74
1
Record Actual Setpoint
Содержание Pro-EC44