Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 150
Operator Access To Setpoint Edit
Value
Operator Access To Edit Loop 1 Setpoint
Dec
4128
20512 41024
RW
0
No
Hex
1020
5020
A040
1
Yes
Loop 1 Selected Setpoint
Value
Selected Setpoint For Loop 1
Dec
4127
20511 41022
RO
0
Main Setpoint
Hex
101F
501F
A03E
1
Alternate setpoint
Loop 1 Actual Setpoint
Effective Setpoint Value Of Selected Loop 1 Setpoint
Dec
8256
24640 49280
RO
The effective setpoint for loop 1
(
current instantaneous value of the active setpoint source
)
Hex
2040
6040
C080
Loop 2 Setpoint Parameters
Parameter Name & Register Address
Integer Int +1
Float
Access
Values
& Descriptions
Loop 2 Setpoint Minimum
Minimum Allowed Setpoint For Loop 2
Dec
3950
20334 40668
RW
Valid between the scaled input lower & upper limits
Hex
0F6E
4F6E
9EDC
Loop 2 Setpoint Maximum
Maximum Allowed Setpoint For Loop 2
Dec
3951
20335 40670
RW
Valid between the scaled input lower & upper limits
Hex
0F6F
4F6F
9EDE
Loop 2 Main Local Setpoint Value
Main Setpoint Value For Loop 2
Dec
3964
20348 40696
RW
Valid between Setpoint Maximum and Minimum
Hex
0F7C
4F7C
9EF8
Loop 2 Main Local Setpoint Offset
Offset Of Main Setpoint Of Loop 2
Dec
3965
20349 40698
RW
Changes effective setpoint (for multi-zone slaves. +ve values
added -ve values subtracted.
Setpoint always limited by Setpoint Max and Min.
Hex
0F7D
4F7D
9EFA
Loop 2 Alternate Local Setpoint Value
Alternate Setpoint Value For Loop 2
Dec
3966
20350 40700
RW
Valid between Setpoint Maximum and Minimum
Hex
0F7E
4F7E
9EFC
Loop 2 Alternate Local Setpoint Offset
Offset Of Alternate setpoint Of Loop 2
Dec
3967
20351 40702
RW
Changes effective setpoint (for multi-zone slaves. +ve values
added -ve values subtracted.
Setpoint always limited by Setpoint Max and Min.
Hex
0F7F
4F7F
9EFE
Loop 2 Main Setpoint Source
Value
Main Setpoint Source For Loop 2
Dec
4052
20436 40872
RW
0
Local Setpoint 1
Hex
0FD4
4FD4
9FA8
1
Not Used
Loop 2 Alternate Setpoint Source
Value
Alternate Setpoint Source For Loop 2
Dec
4053
20437 40874
RW
0
Not Used
Hex
0FD5
4FD5
9FAA
1
Local Setpoint 2
3
Input A Remote Setpoint
Loop 2 Setpoint Select
Value
Setpoint Select For Loop 2
Dec
4200
20584 41168
RW
0
Local Setpoint 1
Hex
1068
5068
A0D0
1
Alternate setpoint
Loop 2 Setpoint Ramp Rate
Setpoint Ramp Rate For Loop 2
Dec
4201
20585 41170
RW
0 to 10000 display units per hour
(1 to 9999 is ramp rate per hour, either 0 or >10000 = Off)
Hex
1069
5069
A0D2
Содержание Pro-EC44
Страница 1: ...Pro EC44 2 Loop Graphical Profile Controller Recorder Pro EC44 User Guide 59540 2 ...
Страница 2: ......
Страница 6: ......