Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 115
31
10 to 50mV DC
32
0 to 5V DC
33
1 to 5V DC
34
0 to 10V DC
35
2 to 10V DC
36
Potentiometer
Input 1 Engineering Units
Value
Engineering Units For Display
Dec
1025
17409 34818
RW
0
=
None
Hex
0401
4401
8802
1
= °C (Default for Europe)
2
= °F (Default for USA)
3
= °K
4
= Bar
5
= pH
6
= %
7
= %RH
8
= PSI
Input 1 Maximum Display Decimal
Places
Value
Maximum Number Of Decimal Places In Display
Dec
1026
17410 34820
RW
0
None (e.g. 1234)
Hex
0402
4402
8804
1
One (e.g. 123.4)
2
Two (e.g. 12.34)
3
Three (e.g. 1.234)
Input 1 Scaled Input Lower Limit
Scaling Value Low Limit
Dec
1027
17411 34822
RW
Valid between input 1 range maximum and minimum
(see
Specifications section for input details)
Hex
0403
4403
8806
Input 1 Scaled Input Upper Limit
Scaling Value High Limit
Dec
1028
17412 34824
RW
Valid between input 1 range maximum and minimum
(see
Specifications section for input details)
Hex
0404
4404
8808
Input 1 Process Variable Offset
Single Point Calibration PV Offset
Dec
1029
17413 34826
RW
Used for Single Point Calibration of input 1
Valid between the scaled input lower & upper limits
Hex
0405
4405
880A
Input 1 Filter Time Constant
Input 1 Process Input Filter Time
Dec
1030
17414 34828
RW
Valid between 0.0 and 512.0
Hex
0406
4406
880C
Input 1 Process Variable
Process Input 1 Value
Dec
1031
17415 34830
RO
The current input 1 process value
Hex
0407
4407
880E
Input 1 Signal /Sensor Break Flag
Value
Process Input Break Status
Dec
1032
17416 34832
RO
0
Inactive
Hex
0408
4408
8810
1
Active
(break detected)
Input 1 Signal Under Range Flag
Value
Process Input Under Range Status
Dec
1033
17417 34834
RO
0
Inactive
Hex
0409
4409
8812
1
Active
(under-range detected)
Input Signal Over Range Flag
Value
Process Input Over Range Status
Dec
1034
17418 34836
RO
0
Inactive
Hex
040A
440A
8814
1
Active
(over-range detected)
Input 1 Cold Junction Compensation
Value
CJC Status
Dec
1035
17419 34838
RW
0
Disabled
Hex
040B
440B
8816
1
Enabled (
default
)