Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014
Page 178
LED 1 Option C Digital Indication
Bit
If bit =1, Digital C
n
status is selected
Dec
7696
24080
48160
RW
0
Digital Input C1
Hex
1E10
5E10
BC20
1
Digital Input C2
2
Digital Input C3
3
Digital Input C4
4
Digital Input C5
5
Digital Input C6
6
Digital Input C7
LED 1 Control Indication
Bit
If bit =1, the function's status is selected
Dec
7644
24028
48056
RW
0
Loop 1 Auto Tune (self-tune=On, pre-tune=flashing)
Hex 1DDC 5DDC
BBB8
1
Loop 1 Manual Control
2
Loop 2 Auto Tune (self-tune=On, pre-tune=flashing)
3
Loop 2 Manual Control
LED 2 Usage
Value
LED 2 Usage.
For 8 & 9 see also LED 2 Selections.
Dec
7665
24049
48098
RW
0
Loop 1 Primary Control ON = LED 1 ON
Hex
1DF1
5DF1
BBE2
1
Loop 1 Secondary Control ON = LED 1 ON
2
Loop 2 Primary Control ON = LED 1 ON
3
Loop 2 Secondary Control ON = LED 1 ON
4
Loop 1 VMD Open ON = LED 1 ON
5
Loop 1 VMD Close ON = LED 1 ON
6
Loop 2 VMD Open ON = LED 1 ON
7
Loop 2 VMD Close ON = LED 1 ON
8
Alarm/Events/Digital/Control (Logical OR of selection
below)
9
Alarm/Events/Digital/Control inverted (Logical NOR of
selection)
Value 8 (Logical
OR
selection of Alarm/Events/Digital/Control) turns
ON
the LED if any of the selected
alarms, events, inputs or functions are active.
Value 9 (Logical
NOR
selection of Alarm/Events/Digital/Control) turns
OFF
the LED if any of the selected
alarms, events, inputs or functions are active.
Note:
Pre-tune will flash the LED instead of turning it on, but flashing will be obscured if used in
conjunction with other functions when they are on.
LED 2 Alarm Indication
Bit
If bit =1, Alarm
n
status is selected
Dec
7698
24082
48164
RW
0
Alarm 1
Hex
1E12
5E12
BC24
1
Alarm 2
2
Alarm 3
3
Alarm 4
4
Alarm 5
5
Alarm 6
6
Alarm 7