Quick Reference of Parameters, Alarms and Faults
0-14 | CFW501
0
Param.
Function
Adjustable Range
Factory Setting
User
Setting Propr.
Groups Pag.
P1020 Main PID P. Gain
0.000 to 32.767
1.000
HVAC
P1021 Main PID I. Gain
0.000 to 32.767
0.430
HVAC
P1022 Main PID D. Gain
0.000 to 32.767
0.000
HVAC
P1023 Main PID Output Min. Value
0.0 to 100.0 %
0.0 %
HVAC
P1024 Main PID Output Max. Value
0.0 to 100.0 %
100.0 %
HVAC
P1025 SoftPLC Parameter 16
-32768 to 32767
0
HVAC
P1026 Main PID Feedback Conf.
0 = Sum Feed. 1 and 2
1 = Difference Feed. 1 and 2
2 = Average Feed. 1 and 2
0
cfg
HVAC
P1027 Main PID Minimum Feedback
-32768 to 32767
0
HVAC
P1028 Main PID Maximum Feedback
-32768 to 32767
1000
HVAC
P1029 SoftPLC Parameter 20
-32768 to 32767
0
HVAC
P1030 Main PID Feedback Alarm Conf.
0 = Disable
1 = Enable Alarm
2 = Enable Fault
0
cfg
HVAC
P1031 Main PID Feedback Alarm Low V.
-32768 to 32767
50
HVAC
P1032 Main PID Feedback Alarm Low T.
0.00 to 650.00 s
5.00 s
HVAC
P1033 Main PID Feedback Alarm High V.
-32768 to 32767
900
HVAC
P1034 Main PID Feedback Alarm High T.
0.00 to 650.00 s
5.00 s
HVAC
P1035 SoftPLC Parameter 26
-32768 to 32767
0
HVAC
P1036 Sleep Mode Speed
0 to 18000
350
HVAC
P1037 Sleep Mode Time
0.00 to 650.00 s
5.00 s
HVAC
P1038 Wake up Mode Deviation
0.0 to 100.0 %
5.0 %
HVAC
P1039 Wake up Mode Time
0.00 to 650.00 s
10.00 s
HVAC
P1040 HVAC Func. Logical Status
0 to 65535
ro
HVAC
P1041 SoftPLC Parameter 32
-32768 to 32767
0
HVAC
P1042 Dry Pump Config.
0 = Disable
1 = Enable Alarm
2 = Enable Fault
0
cfg
HVAC
P1043 Dry Pump Speed
0 to 18000
400
HVAC
P1044 Dry Pump Torque
0.0 to 350.0 %
20.0 %
HVAC
P1045 Dry Pump Time
0.00 to 650.00 s
20.00 s
HVAC
P1046 Broken Belt Conf.
0 = Disable
1 = Enable Alarm
2 = Enable Fault
0
cfg
HVAC
P1047 Broken Belt Speed
0 to 18000
400
HVAC
Содержание CFW501 V1.8X
Страница 2: ......
Страница 8: ...Summary...
Страница 34: ...General Information 2 4 CFW501 2...
Страница 38: ...About the CFW501 3 4 CFW501 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW501 4...
Страница 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Страница 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Страница 76: ...Available Motor Control Types 8 4 CFW501 8...
Страница 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Страница 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Страница 148: ...Faults and Alarms 14 12 CFW501 14...