0
Quick Reference of Parameters, Alarms and Faults
CFW501 | 0-9
0
Param.
Function
Adjustable Range
Factory Setting
User
Setting Propr.
Groups Pag.
P0289 Ny Speed
0 to 18000 rpm
1800 (1500) rpm
I/O
P0290 Ix Current
0.0 to 200.0 A
1.0xI
nom
I/O
P0291 Zero Speed
0 to 18000 rpm
18 (15) rpm
I/O
P0292 N = N* Band
0 to 18000 rpm
18 (15) rpm
I/O
P0293 Tx Torque
0 to 200 %
100 %
I/O
P0294 Hx Time
0 to 6553.5 h
432.0 h
I/O
P0295 Inverter Rated Current
0.0 to 200.0 A
According to
inverter model
ro
READ
P0296 Line Rated Voltage
0 = 200 - 240 V
1 = 380 - 480 V
2 = 500 - 600 V
According to
inverter model
ro
READ
P0297 Switching Frequency
2500 to 15000 Hz
5000 Hz
MOTOR
P0299 DC-Braking Start Time
0.0 to 15.0 s
0.0 s
MOTOR
P0300 DC-Braking Stop Time
0.0 to 15.0 s
0.0 s
MOTOR
P0301 DC-Braking Speed
0 to 18000 rpm
30 rpm
MOTOR
P0302 DC-Braking Voltage
0.0 to 100.0 %
20.0 %
MOTOR
P0303 Skip Speed 1
0 to 18000 rpm
600 rpm
P0304 Skip Speed 2
0 to 18000 rpm
900 rpm
P0306 Skip Band
0 to 18000 rpm
0 rpm
P0308 Serial Address
0 to 255
1
NET
P0310 Serial Baud Rate
0 = 9600 bits/s
1 = 19200 bits/s
2 = 38400 bits/s
1
NET
P0311 Serial Bytes Config.
0 = 8 bits, no, 1
1 = 8 bits, even,1
2 = 8 bits, odd, 1
3 = 8 bits, no, 2
4 = 8 bits, even,2
5 = 8 bits, odd, 2
1
NET
P0312 Serial Protocol(1)(2)
0 = HMI(1)
1 = Reserved
2 = Modbus RTU(1)
3 = BACnet(1)
4 = N2(1)
5 = Reserved
6 = HMI(1)/Modbus RTU(2)
7 = Modbus RTU(2)
8 = HMI(1)/BACnet(2)
9 = BACnet(2)
10 = HMI(1)/N2(2)
11 = N2(2)
2
cfg
NET
P0313 Comm. Error Action
0 = Inactive
1 = Ramp Stop
2 = General Disab.
3 = Go to LOC
4 = LOC Keep Enab.
5 = Cause Fault
1
NET
P0314 Serial Watchdog
0.0 to 999.0 s
0.0 s
NET
P0316 Serial Interf. Status
0 = Inactive
1 = Active
2 = Watchdog Error
ro
NET
P0320 FlyStart/Ride-Through
0 = Inactive
1 = Flying Start
2 = FS / RT
3 = Ride-Through
0
cfg
P0331 Voltage Ramp
0.2 to 60.0 s
2.0 s
P0340 Auto-Reset Time
0 to 255 s
0 s
Содержание CFW501 V1.8X
Страница 2: ......
Страница 8: ...Summary...
Страница 34: ...General Information 2 4 CFW501 2...
Страница 38: ...About the CFW501 3 4 CFW501 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW501 4...
Страница 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Страница 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Страница 76: ...Available Motor Control Types 8 4 CFW501 8...
Страница 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Страница 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Страница 148: ...Faults and Alarms 14 12 CFW501 14...