Functions Common to all the Control Modes
11-10 | CFW501
11
11.3.2 Ride-Through Function
The Ride-Through function will disable the inverter output pulses (IGBT) as soon as the supply voltage reaches a
value below the undervoltage value. A fault due to undervoltage (F0021) does not occur and the DC link voltage
will slowly drop until the supply voltage returns. In case it takes the supply voltage too long to return (over 2
seconds), the inverter may indicate F0021 (undervoltage on the DC link). If the supply voltage returns before, the
inverter will enable the pulses again, imposing the speed reference instantly (like in the Flying Start function) and
making a voltage ramp with time defined by parameter P0331. Refer to
Figure 11.7: Actuation of the Ride-Through
.
DC link voltage
F021 Level
Output pulses
t
desab.
> t
dead
Enabled
Disabled
Return line
Output voltage
0 V
0 rpm
Output speed
(P0002)
P0331
Figure 11.7:
Actuation of the Ride-Through function
The Ride-Through function allows recovering the inverter without locking by undervoltage F0021 for momentary
power supply drops. The time interval accepted during a fault is at most two seconds.
11.4 DC BRAKING
The DC braking allows stopping the motor by applying direct current to it. The current applied at the DC braking is
proportional to the braking torque and may be set in P0302. It is set in percentage (%) of the inverter rated current
considering the motor of power compatible with the inverter.
P0299 – DC Braking Time at Start
Adjustable
Range:
0.0 to 15.0 s
Factory
Setting:
0.0 s
Properties:
Access groups
via HMI:
MOTOR
Description:
DC braking duration at the start.
Содержание CFW501 V1.8X
Страница 2: ......
Страница 8: ...Summary...
Страница 34: ...General Information 2 4 CFW501 2...
Страница 38: ...About the CFW501 3 4 CFW501 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW501 4...
Страница 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Страница 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Страница 76: ...Available Motor Control Types 8 4 CFW501 8...
Страница 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Страница 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Страница 148: ...Faults and Alarms 14 12 CFW501 14...