Quick Reference of Parameters, Alarms and Faults
0-10 | CFW501
0
Param.
Function
Adjustable Range
Factory Setting
User
Setting Propr.
Groups Pag.
P0343 Mask for Faults and Alarms
0000 to FFFFh
Bit 0 = F0074
Bit 1 = F0048
Bit 2...3 = Reserved
Bit 4 = F0076
Bit 5....15 = Reserved
0003h
cfg
P0349 Ixt Alarm Level
70 to 100 %
85 %
cfg
P0397 Control Config
0000 to FFFFh
Bit 0 = Slip Compens. Regen.
Bit 1 = Dead Time Compens.
Bit 2 = Io Stabilization
Bit 3 = P0297 Reduction
Temperature
000Bh
cfg
P0398 Motor Service Factor
1.00 to 1.50
1.00
cfg
MOTOR,
STARTUP
P0399 Motor Rated Eff.
50.0 to 99.9 %
75.0 %
cfg,
V V W
MOTOR,
STARTUP
P0400 Motor Rated Voltage
200 to 600 V
220(230) V
(P0296 = 0)
380(400) V
(P0296 = 1)
575(525) V
(P0296 = 2)
cfg
MOTOR,
STARTUP
P0401 Motor Rated Current
0 to 200.0 A
1.0xI
nom
cfg
MOTOR,
STARTUP
P0402 Motor Rated Speed
0 to 30000 rpm
1710 (1425) rpm
cfg
MOTOR,
STARTUP
P0403 Motor Rated Frequency
0 to 500 Hz
60 (50) Hz
cfg
MOTOR,
STARTUP
P0404 Motor Rated Power
0 = 0.16 hp 0.12 kW
1 = 0.25 hp 0.19 kW
2 = 0.33 hp 0.25 kW
3 = 0.5 hp 0.37 kW
4 = 0.75 hp 0.55 kW
5 = 1 hp 0.75 kW
6 = 1.5 hp 1.1 kW
7 = 2 hp 1.5 kW
8 = 3 hp 2.2 kW
9 = 4 hp 3 kW
10 = 5 hp 3.7 kW
11 = 5.5 hp 4 kW
12 = 6 hp 4.5 kW
13 = 7.5 hp 5.5 kW
14 = 10 hp 7.5 kW
15 = 12.5 hp 9 kW
16 = 15 hp 11 kW
17 = 20 hp 15 kW
18 = 25 hp 18.5 kW
19 = 30 hp 22 kW
According to
inverter model
cfg
MOTOR,
STARTUP
P0407 Motor Rated Power Fac
0.50 to 0.99
0.80
cfg
MOTOR,
STARTUP
P0408 Run Self-Tuning
0 = Inactive
1 = No Rotation
0
cfg,
V V W
STARTUP
P0409 Stator Resistance
0.01 to 99.99
According to
inverter model
cfg,
V V W
MOTOR,
STARTUP
Содержание CFW501 V1.8X
Страница 2: ......
Страница 8: ...Summary...
Страница 34: ...General Information 2 4 CFW501 2...
Страница 38: ...About the CFW501 3 4 CFW501 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW501 4...
Страница 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Страница 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Страница 76: ...Available Motor Control Types 8 4 CFW501 8...
Страница 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Страница 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Страница 148: ...Faults and Alarms 14 12 CFW501 14...