Quick Reference of Parameters, Alarms and Faults
0-12 | CFW501
0
Param.
Function
Adjustable Range
Factory Setting
User
Setting Propr.
Groups Pag.
P0513 Indirect Indication Form 2
0 = wxyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
1
HMI
P0516 Ref. Eng. Unit 4
See options in P0510
13
HMI
P0517 Indirect Indication Form 4
0 = wxyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
1
HMI
P0580 Fire Mode Configuration
0 = Inactive
1 = Active
2 = Active / P0134
3 = Active / P0581
4 = Active / Gen. Disable
0
cfg
HVAC
P0581 Setpoint PID fire Mode
-32768 to 32767
0
HVAC
P0582 Auto-reset configuration
0 = Limited
1 = Unlimited
0
cfg
HVAC
P0583 Bypass Mode Configuration
0 = Inactive
1 = Active/DIx
2 = Active/DIx+Failure
0
cfg
HVAC
P0584 Bypass Contactor time
0.00 to 300.00 s
0.30 s
cfg
HVAC
P0585 Short Cycle Protection Config.
0 = Inactive
1 = Active
0
cfg
HVAC
P0586 Minimum RUN Time
0 to 650.00 s
5.00 s
cfg
HVAC
P0587 Minimum STOP Time
0.00 to 650.00 s
5.00 s
cfg
HVAC
P0588 Energy Saving Max. Torque
0 to 85 %
60 %
cfg, V/f
HVAC
P0589 Energy Saving Min. Mag.
40 to 80 %
40 %
cfg, V/f
HVAC
P0590 Energy Saving Min. Speed
360 to 18000 rpm
600 (525) rpm
cfg, V/f
HVAC
P0591 Energy Saving Hysteresis
0 to 30 %
10 %
cfg, V/f
HVAC
P0680 Logical Status
Bit 0 = Not Used
Bit 1 = Run Command
Bit 2 = Fire mode
Bit 3 = Bypass
Bit 4 = Quick Stop
Bit 5 = 2
nd
Ramp
Bit 6 = Config. Mode
Bit 7 = Alarm
Bit 8 = Running
Bit 9 = Enabled
Bit 10 = Forward
Bit 11 = JOG
Bit 12 = Remote
Bit 13 = Subvoltage
Bit 14 = Reserved
Bit 15 = Fault
ro
READ,
NET
P0681 Speed in 13 bits
-32768 to 32767
ro
NET
P0682 Serial/USB Control
Bit 0 = Ramp Enable
Bit 1 = General Enable
Bit 2 = Run Forward
Bit 3 = JOG Enable
Bit 4 = Remote
Bit 5 = 2
nd
Ramp
Bit 6 = Quick Stop
Bit 7 = Fault Reset
Bit 8....12 = Not Used
Bit 13 = Intern PID
Bit 14 = Extern PID
Bit 15 = Reserved
ro
NET
P0683 Serial/USB Speed Ref.
-32768 to 32767
ro
NET
Содержание CFW501 V1.8X
Страница 2: ......
Страница 8: ...Summary...
Страница 34: ...General Information 2 4 CFW501 2...
Страница 38: ...About the CFW501 3 4 CFW501 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW501 4...
Страница 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Страница 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Страница 76: ...Available Motor Control Types 8 4 CFW501 8...
Страница 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Страница 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Страница 148: ...Faults and Alarms 14 12 CFW501 14...