0
Quick Reference of Parameters, Alarms and Faults
CFW501 | 0-3
0
Param.
Function
Adjustable Range
Factory Setting
User
Setting Propr.
Groups Pag.
P0075 Log. State 3
rd
Fault
0000h to FFFFh
ro
READ
P0080 Last Fault in “Fire Mode”
0 to 999
0
ro
READ
P0081 Second Fault in “Fire Mode”
0 to 999
0
ro
READ
P0082 Third Fault in “Fire Mode”
0 to 999
0
ro
READ
P0100 Acceleration Time
0.1 to 999.0 s
10.0 s
BASIC
P0101 Deceleration Time
0.1 to 999.0 s
10.0 s
BASIC
P0102 2
nd
Ramp Accel. Time
0.1 to 999.0 s
10.0 s
P0103 2
nd
Ramp Decel. Time
0.1 to 999.0 s
10.0 s
P0104 S Ramp
0 = Inactive
1 = Active
0
cfg
P0105 1
st
/2
nd
Ramp Sel.
0 = 1
st
Ramp
1 = 2
nd
Ramp
2 = DIx
3 = Serial/USB
4 = SoftPLC
2
I/O
P0106 3
rd
Ramp Time
0.1 to 999.0 s
5.0 s
P0120 Speed Ref. Backup
0 = Inactive
1 = Active
2 = Backup by P0121
1
P0121 Keypad Reference
0 to 18000 rpm
90 rpm
P0122 JOG Reference
0 to 18000 rpm
150 (125) rpm
P0133 Minimum Speed
0 to 18000 rpm
90 (75) rpm
BASIC
P0134 Maximum Speed
0 to 18000 rpm
1800 (1500) rpm
BASIC
P0135 Max. Output Current
0.0 to 200.0 A
1.5xI
nom
V/f, V V W
BASIC,
MOTOR
P0136 Manual Torque Boost
0.0 to 30.0 %
According to
inverter model
V/f
BASIC,
MOTOR
P0137 Autom. Torque Boost
0.0 to 30.0 %
0.0 %
V/f
MOTOR
P0138 Slip Compensation
-10.0 to 10.0 %
0.0 %
V/f
MOTOR
P0139 Output Current Filter
0 to 9999 ms
50 ms
P0140 Sleep Compensation Filter
0 to 9999 ms
500 ms
V V W
P0142 Max. Output Voltage
0.0 to 100.0 %
100.0 %
cfg, V/f
P0143 Interm.Output Voltage
0.0 to 100.0 %
66.7 %
cfg, V/f
P0144 Low Output Voltage
0.0 to 100.0 %
33.3 %
cfg, V/f
P0145 Field Weakening Speed
0 to 18000 rpm
1800 (1500) rpm
cfg, V/f
P0146 Intermediate Speed
0 to 18000 rpm
1200 (1000) rpm
cfg, V/f
P0147 Low Speed point
0 to 18000 rpm
600 (500) rpm
cfg, V/f
P0150 Ud Regul. Type V/f and Current
Limitation
0 = hold_Ud and desac_LC
1 = acel_Ud and desac_LC
2 = hold_Ud and hold_LC
3 = acel_Ud and hold_LC
0
cfg, V/f,
V V W
MOTOR
P0151 DC Regul. Level V/f
339 to 1200 V
400 V (P0296 = 0)
800 V (P0296 = 1)
1000 V (P0296 = 2)
V/f, V V W MOTOR
P0152 DC Link Regul. P Gain
0.00 to 9.99
1.50
V/f, V V W MOTOR
P0153 Dyn. Braking Level
339 to 1200 V
375 V (P0296 = 0)
750 V (P0296 = 1)
950 V (P0296 = 2)
V/f, V V W MOTOR
P0156 Overl.Curr. 100 % Speed
0.0 to 200.0 A
1.1xI
nom
MOTOR
P0157 Overl.Curr. 50 % Speed
0.0 to 200.0 A
1.0xI
nom
MOTOR
P0158 Overl.Curr. 20 % Speed
0.0 to 200.0 A
0.8xI
nom
MOTOR
P0178 Rated Flux
0.0 to 150.0 %
100.0 %
MOTOR
P0200 Password
0 = Inactive
1 = Active
1 to 19999 = New password
0
HMI
P0202 Type of Control
0 to 2 = V/f
3 = V V W
0
cfg
STARTUP
Содержание CFW501 V1.8X
Страница 2: ......
Страница 8: ...Summary...
Страница 34: ...General Information 2 4 CFW501 2...
Страница 38: ...About the CFW501 3 4 CFW501 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW501 4...
Страница 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Страница 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Страница 76: ...Available Motor Control Types 8 4 CFW501 8...
Страница 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Страница 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Страница 148: ...Faults and Alarms 14 12 CFW501 14...