SoftPLC
CFW501 | 17-1
17
17 SOFTPLC
The SoftPLC function allows the inverter to assume PLC (Programmable Logical Controller). For further details
regarding the programming of those functions in the CFW501, refer to the CFW501 SoftPLC manual. Below are
described the parameters related to the SoftPLC.
P1000 – SoftPLC Status
Adjustable
Range:
0 = No App.
1 = Installing App.
2 = Incompat. App.
3 = App. Stopped
4 = App. Running
Factory
Setting:
Properties:
ro
Access groups
via HMI:
HVAC
Description:
It allows the user to view the status in which the SoftPLC is. If there are no applications installed, the parameters
P1001 to P1079 will not be shown on the HMI.
If this parameter presents the option 2 (“Incompat. App.”), it indicates that the version that was uploaded to the
flash memory board is not compatible with the present CFW501 firmware.
In this case, it is necessary that the user recompile the project on the WLP, considering the new CFW501
version and redo the download. The user can also upload the application from the inverter to a PC via WLP,
provided that the application password is known, or that the application has no password associated.
P1001 – Command for SoftPLC
Adjustable
Range:
0 = For application
1 = Executes application
2 = Excludes application
Factory
Setting:
1
Properties:
cfg
Access groups
via HMI:
HVAC
Description:
This parameter allows stopping, running or excluding an application installed, but to do so, the motor must be
disabled.
P1002 – Scan Cycle Time
Adjustable
Range:
0 to 65535 ms
Factory
Setting:
Properties:
ro
Access groups
via HMI:
HVAC
Description:
These parameter sets the application scanning time. The larger the application, the longer is the scanning time.
Содержание CFW501 V1.8X
Страница 2: ......
Страница 8: ...Summary...
Страница 34: ...General Information 2 4 CFW501 2...
Страница 38: ...About the CFW501 3 4 CFW501 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW501 4...
Страница 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Страница 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Страница 76: ...Available Motor Control Types 8 4 CFW501 8...
Страница 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Страница 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Страница 148: ...Faults and Alarms 14 12 CFW501 14...