HVAC Functions
18-10 | CFW501
18
P1017 – Main PID Controller Action Control
Adjustable
Range:
0 = Disable PID
1 = Direct Mode
2 = Reverse Mode
Factory
Setting:
0
Properties:
cfg
Access groups
via HMI:
HVAC
Description:
This parameter defines how the action control or regulation of Main PID controller.
Table 18.4:
Description of Main PID controller action control
P1017
Description
0
It defines the Main PID controller will be disabled to operation.
1
It defines the Main PID controller action control or regulation will be enabled in direct mode.
2
It defines the Main PID controller action control or regulation will be enabled in reverse mode.
NOTE!
In situations that, in order to increase the value of the process variable, it is necessary to increase
the output of the PID controller, the control action of the PID controller must be set to direct mode.
E.g.: Pump driven by an inverter and filling a tank. For the level of the tank (process variable) to increase,
it is necessary that the flow increase, which is accomplished by increasing the speed of the motor. In
situations that, in order to increase the value of the process variable, it is necessary to decrease the
output of the PID controller, the control action of the PID controller must be set to reverse mode. E.g.:
Fan driven by the inverter cooling down a cooling tower. When an increase in temperature is desired
(process variable), it is necessary to reduce the ventilation by reducing the motor speed.
Содержание CFW501 V1.8X
Страница 2: ......
Страница 8: ...Summary...
Страница 34: ...General Information 2 4 CFW501 2...
Страница 38: ...About the CFW501 3 4 CFW501 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW501 4...
Страница 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Страница 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Страница 76: ...Available Motor Control Types 8 4 CFW501 8...
Страница 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Страница 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Страница 148: ...Faults and Alarms 14 12 CFW501 14...