V/f Scalar Control
CFW501 | 9-5
9
P0142 – Maximum Output Voltage
P0143 – Intermediate Output Voltage
P0144 – Minimum Output Voltage
Adjustable
Range:
0.0 to 100.0 %
Factory
Setting:
P0142 = 100.0 %
P0143 = 66.7 %
P0144 = 33.3 %
Properties:
cfg, V/f
Description:
These parameters allow adjusting the inverter V/f curve together with its orderly pairs P0145, P0146 and P0147.
P0145 – Field Weakening Start Speed
P0146 – Intermediate Output Speed
P0147 – Minimum Output Speed
Adjustable
Range:
0.0 to 18000
Factory
Setting:
P0145 = 1800
(1500) rpm
P0146 = 1200
(1000) rpm
P0147 = 600
(500) rpm
Properties:
cfg, V/f
Description:
These parameters allow adjusting the inverter V/f curve together with its orderly pairs P0142, P0143 and P0144.
The V/f curve can be adjusted in applications where the motor rated voltage is smaller than the power supply
voltage, for instance, in a 440 V power supply with 380 V motor.
The adjustment of the V/f curve is necessary when a quadratic approximation is desired for energy saving in
centrifugal pumps and fans, or in special applications: when a transformer is used between the inverter and the
motor or the inverter is used as a power supply.
Содержание CFW501 V1.8X
Страница 2: ......
Страница 8: ...Summary...
Страница 34: ...General Information 2 4 CFW501 2...
Страница 38: ...About the CFW501 3 4 CFW501 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW501 4...
Страница 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Страница 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Страница 76: ...Available Motor Control Types 8 4 CFW501 8...
Страница 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Страница 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Страница 148: ...Faults and Alarms 14 12 CFW501 14...