V/f Scalar Control
9-4 | CFW501
9
P0136 – Manual Torque Boost
Adjustable
Range:
0.0 to 30.0 %
Factory
Setting:
According
to inverter
model
Properties:
V/f
Access groups
via HMI:
BASIC, MOTOR
Description:
This parameter actuates in low speeds, that is, in the range from 0 to P0147, increasing the inverter output
voltage to compensate the voltage drop in the motor stator resistance so as to keep the torque constant.
The optimum setting is the smallest value of P0136 which allows the motor satisfactory start. A value greater
than necessary will excessively increase the motor current at low speeds, which may lead the inverter to a fault
condition (F0048, F0051 or F0070) or alarm condition (A0046, A0047 or A0050), as well as motor overheating.
Figure 9.3: Torque boost region on page 9-4
shows the region of actuation of the Torque Boost between
points P
0
and P
1
.
P0134
P0145
P0146
P0147
P
0
P
1
P
2
P
3
P
4
P0142
P0143
P0144
P0136
Output
speed (rpm)
Output
voltage (%)
Figure 9.3:
Torque boost region
Содержание CFW501 V1.8X
Страница 2: ......
Страница 8: ...Summary...
Страница 34: ...General Information 2 4 CFW501 2...
Страница 38: ...About the CFW501 3 4 CFW501 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW501 4...
Страница 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Страница 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Страница 76: ...Available Motor Control Types 8 4 CFW501 8...
Страница 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Страница 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Страница 148: ...Faults and Alarms 14 12 CFW501 14...