HVAC Functions
CFW501 | 18-13
18
P1023 – Main PID Controller Output Minimum Value
Adjustable
Range:
0.0 to 100.0 %
Factory
Setting:
0.0 %
Properties:
Access groups
via HMI:
HVAC
Description:
This parameter defines the minimum output value of the Main PID controller.
P1024 – Main PID Controller Output Maximum Value
Adjustable
Range:
0.0 to 100.0 %
Factory
Setting:
100.0 %
Properties:
Access groups
via HMI:
HVAC
Description:
This parameter defines the maximum output value of the Main PID controller.
P1026 – Configuration of the Process Variable of the Main PID Controller
Adjustable
Range:
0 = Sum of the feedbacks 1 and 2
1 = Difference between the feedbacks 1 and 2
2 = Average value of the feedbacks 1 and 2
Factory
Setting:
0
Properties:
cfg
Access groups
via HMI:
HVAC
Description:
This parameter defines some functionalities for the analog input(s) selected for the feedback 1 and 2 of the main
PID controller.
Table 18.6:
Configuration of the Process Variable of the Main PID Controller
P1026
Description
0
It defines that the process variable of the main PID controller will be the sum of feedbacks 1 and 2.
1
It defines that the process variable of the main PID controller will be the difference of feedbacks 1 and 2.
2
It defines that the process variable of the main PID controller will be the average of feedbacks 1 and 2.
Содержание CFW501 V1.8X
Страница 2: ......
Страница 8: ...Summary...
Страница 34: ...General Information 2 4 CFW501 2...
Страница 38: ...About the CFW501 3 4 CFW501 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW501 4...
Страница 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Страница 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Страница 76: ...Available Motor Control Types 8 4 CFW501 8...
Страница 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Страница 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Страница 148: ...Faults and Alarms 14 12 CFW501 14...