CFW-09 -
QUICK PARAMETER REFERENCE
10
Parameters
Function
Adjustable Range
Factory
Unit
User's
Page
Setting
Setting
(*)
P136 has different functions for V/F and Vector Control.
P060
Fifth Error
0 to 71
-
123
P061
Sixth Error
0 to 71
-
123
P062
Seventh Error
0 to 71
-
123
P063
Eighth Error
0 to 71
-
123
P064
Ninth Error
0 to 71
-
123
P065
Tenth Error
0 to 71
-
123
P070
Motor Current and Motor Speed
0 to 2600
A (rms)
123
0 to P134
rpm
P071
Command Word
0 a 65535
-
123
P072
Fieldbus Speed Reference
0 a 65535
-
123
REGULATION PARAMETERS
P100 to P199
Ramps
P100
Acceleration Time
0.0 to 999
20.0
s
124
P101
Deceleration Time
0.0 to 999
20.0
s
124
P102
Acceleration Time 2
0.0 to 999
20.0
s
124
P103
Deceleration Time 2
0.0 to 999
20.0
s
124
P104
S Ramp
0 = Inactive (Linear)
0 = Inactive
-
124
1 = 50 %
2 = 100 %
Speed References
P120
Speed Reference Backup
0 = Inactive
1 = Active
-
124
1 = Active
P121
Keypad Speed Reference
P133 to P134
90
rpm
125
P122
(2) (11)
JOG or JOG+ Speed Reference
00 to P134
150 (125)
rpm
125
P123
(2) (11)
JOG- Speed Reference
00 to P134
150 (125)
rpm
125
P124
(2) (11)
Multispeed Reference 1
P133 to P134
90 (75)
rpm
126
P125
(2) (11)
Multispeed Reference 2
P133 to P134
300 (250)
rpm
126
P126
(2) (11)
Multispeed Reference 3
P133 to P134
600 (500)
rpm
126
P127
(2) (11)
Multispeed Reference 4
P133 to P134
900 (750)
rpm
126
P128
(2) (11)
Multispeed Reference 5
P133 to P134
1200 (1000)
rpm
126
P129
(2) (11)
Multispeed Reference 6
P133 to P134
1500 (1250)
rpm
126
P130
(2) (11)
Multispeed Reference 7
P133 to P134
1800 (1500)
rpm
126
P131
(2) (11)
Multispeed Reference 8
P133 to P134
1650 (1375)
rpm
126
Speed Limits
P132
(1)
Maximum Overspeed Level
(0 to 99) x P134
10
%
127
100 = Disabled
P133
(2) (11)
Minimum Speed Reference
0 to (P134-1)
90 (75)
rpm
127
P134
(2) (11)
Maximum Speed Reference
(P133+1) to (3.4 x P402)
1800 (1500)
rpm
127
I/F Control
P135
(2)
Speed transition to I/F Control
0 to 90
18
rpm
128
P136
(*)
Current Reference (I*)
0 = I
mr
1 = 1.11 x I
mr
-
128
for I/F Control
1 = 1.11 x I
mr
2 = 1.22 x I
mr
3 = 1.33 x I
mr
4 = 1.44 x I
mr
5 = 1.55 x I
mr
6 = 1.66 x I
mr
7 = 1.77 x I
mr
8 = 1.88 x I
mr
9 = 2.00 x I
mr