70
CHAPTER 3 - INSTALLATION AND CONNECTION
Maximum motor cable length
according to conducted
emission class (EN61800-3)
Inverter Model
Load
Type
Epcos Input Filter
Class
A2
Class
A1
Class
B
Inside metallic
panel
Electromagnetic radiation
disturbance level
(Product Standard
EN61800-3 (1996)+A11
(2000))
CT
107 A/500-690 V
VT
First environment,
restricted distribution
CT
B84143B150S21
147 A/500-690 V
VT
First environment,
restricted distribution
211 A/500-690 V
CT/VT
B84143B250S21
First environment,
restricted distribution
CT
247 A/500-690 V
VT
Second environment,
unrestricted distribution
CT
315 A/500-690 V
VT
Second environment,
unrestricted distribution
CT
343 A/500-690 V
VT
B84143B400S125
Second environment,
unrestricted distribution
CT
418 A/500-690 V
VT
Second environment,
unrestricted distribution
CT
472 A/500-690 V
VT
B84143B600S125
100 m
25 m
N/A
YES
Second environment,
unrestricted distribution
500-600 V power supply:
Table 3.10
- Epcos filters list for CFW-09 inverter series with 500-600 V power supply
N/A = Not Applicable – The inverters were not tested with these limits.
Note:
Minimum output frequency = 2.4 Hz.
Maximum motor cable
length according to
conducted emission class
(EN61800-3)
Inverter Model
Load
Type
Epcos Input Filter
Class
A2
Class
A1
Class
B
Inside metallic
panel
Electromagnetic
radiation disturbance
level (Product Standard
EN61800-3 (1996)+A11
(2000))
CT
100 A/660-690 V and
107 A/500-690 V
VT
First environment,
restricted distribution
CT
B84143B150S21
127 A/660-690 V and
147 A/500-690 V
VT
First environment,
restricted distribution
179 A/660-690 V and
211 A/500-690 V
CT/VT
B84143B180S21
First environment,
restricted distribution
CT
225 A/660-690 V and
247 A/500-690 V
VT
Second environment,
unrestricted distribution
CT
259 A/660-690 V and
315 A/500-690 V
VT
Second environment,
unrestricted distribution
CT
305 A/660-690 V and
343 A/500-690 V
VT
Second environment,
unrestricted distribution
CT
B84143B400S125
340 A/660-690 V and
418 A/500-690 V
VT
Second environment,
unrestricted distribution
428 A/660-690 V and
472 A/500-690 V
CT/VT
B84143B600S125
100 m
25 m
N/A
YES
Second environment,
unrestricted distribution
660-690 V power supply:
Table 3.11
- Epcos filters list for CFW-09 inverter series with 660-690 V power supply
N/A = Not Applicable – The inverters were not tested with these limits.
Note:
Minimum output frequency = 2.4 Hz.