CHAPTER 5 - START-UP
ACTION
LED DISPLAY
DESCRIPTION
LCD DISPLAY
Moto r
Rated
Volt
P400 = 380 V
Motor Rated Voltage Range:
0 to 690 V
Programmed Motor Rated Voltage:
460 V
Exit the programming mode
Motor Rated Current Range:
(0.0 to 1.30) x P295
(1)
Enter the programming mode
Programmed Motor Rated Current:
7.9 A
Exit the programming mode
Motor Rated Frequency Range:
0 to 300 Hz
Press the
key to save the
selected option and start the tuning
routine after changing to Vector
Control Mode
Press the
key and use the
and
keys to set the
correct motor rated voltage value
Press the
key to save the
programmed value and exit the
programming mode
Press the
key to go to the
next parameter
Press the
key to enter the
programming mode
Use the
and
keys to set
the correct motor rated current value
Press the
key to save the
programmed value and exit the
programming mode
Press the
key to go to the
next parameter
Moto r
Rated
Volt
P400 = 460 V
Moto r
Rated
Volt
P400 = 460 V
Mo to r R at ed Cur.
P401 = 7.9 A
Mo to r R at ed Cur.
P401 = 7.9 A
Mo to r
R at ed Cur.
P401 = 7.9 A
Mo to r
R at ed Cur.
P401 = 7.9 A
Moto r Rated Freq
P403 = 60 Hz