127
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter
Unit
Description / Notes
When the effective overspeed exceeds the value of P134+P132 longer
than 20 ms, the CFW-09 will disable the PWM pulses by E17.
The P132 setting is a value in percent of P134.
When programmed P132 = 100 %, this function remains disabled.
P132
(1)
0 to 100
Maximum
[ 10 ]
Overspeed Level
1 %
Define the maximum and minimum motor operation speed reference.
Are valid for any type of speed reference signal.
For more details about the actuation of P133 refer to P233 (Analog
Inputs Dead Zone).
P133
(2) (11)
0.0 to (P134-1)
Minimum Speed
[ 90 (75) ]
Reference
1 rpm
P134
(2) (11)
(P133 + 1) to (3.4 x P402)
Maximum Speed
[ 1800 (1500) ]
Reference
1 rpm
Figure 6.2
- Multispeed
Accel. Ramp
Time
24 V
DI6
DI5
DI4
0 V (Open)
24 V
0 V (Open)
24 V
0 V (Open)
P124
P125
P126
P127
P128
P129
P130
P131
Speed
P134
P133
+10 V
-P133
-P134
-10 V
Speed
Reference
Speed
a)