CFW-09 -
QUICK PARAMETER REFERENCE
27
Parameters
Function
Adjustable Range
Factory
Unit
User's
Page
Setting
Setting
0 = for models
220-230 V
3 = for models
380-480 V
6 = for models
500-600 V and
500-690 V
8 = for models
660-690 V
P296
(1) (11)
Inverter Rated Voltage
0 = 220-230 V
-
195
(Rated Input Voltage)
1 = 380 V
2 = 400-415 V
3 = 440-460 V
4 = 480 V
5 = 500-525 V
6 = 550-575 V
7 = 600 V
8 = 660-690 V
P297
(1) (2)
Switching Frequency
0 = 1.25
2 = 5.0
kHz
195
1 = 2.5
2 = 5.0
3 = 10.0
DC Braking
P300
DC Braking Time
0.0 to 15.0
0.0
s
196
P301
DC Braking Start Speed
0 to 450
30
rpm
197
P302
DC Braking Voltage
0.0 to 10.0
2.0
%
197
Skip Speed
P303
Skip Speed 1
P133 to P134
600
rpm
197
P304
Skip Speed 2
P133 to P134
900
rpm
197
P305
Skip Speed 3
P133 to P134
1200
rpm
197
P306
Skip Band
0 to 750
0
rpm
197
Serial Communication
P308
(1)
Inverter Address
1 to 30
1
-
198
P309
(1)
Fieldbus
0 = Disable
0 = Disable
-
198
1 = Profibus DP/DP-V1 2 I/O
2 = Profibus DP/DP-V1 4 I/O
3 = Profibus DP/DP-V1 6 I/O
4 = DeviceNet 2 I/O
5 = DeviceNet 4 I/O
6 = DeviceNet 6 I/O
7 = EtherNet/IP 2 I/O
8 = EtherNet/IP 4 I/O
9 = EtherNet/IP 6 I/O
10 = DeviceNet Drive Profile
P310
(1)
STOP Detection in a Profibus
0 = Off
0 = Off
198
Network
1 = On
P312
(1)
Type of Serial Protocol
0 = WBUS Protocol
0 = WEG Protocol
-
199
1 = Modbus-RTU, 9600 bps,
no parity
2 = Modbus-RTU, 9600 bps,
odd parity
3 = Modbus-RTU, 9600 bps,
even parity
4 = Modbus-RTU, 19200 bps,
no parity
5 = Modbus-RTU, 19200 bps,
odd parity
Attention!
Refer to
item
3.2.3 to
do the
voltage