WAGO-I/O-SYSTEM 750 XTR
I/O Modules 229
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Output Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Controls
DO 8
Channel 8
Controls
DO 7
Channel 7
Controls
DO 6
Channel 6
Controls
DO 5
Channel 5
Controls
DO 4
Channel 4
Controls
DO 3
Channel 3
Controls
DO 2
Channel 2
Controls
DO 1
Channel 1
12.2.3.3 16-Channel Digital Output Modules
Table 264: 16-Channel Digital Output Modules
Output Process Image
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Con-
trols
DO 16
Chan-
nel
16
Con-
trols
DO 15
Chan-
nel
15
Con-
trols
DO 14
Chan-
nel
14
Con-
trols
DO 13
Chan-
nel
13
Con-
trols
DO 12
Chan-
nel
12
Con-
trols
DO 11
Chan-
nel
11
Con-
trols
DO 10
Chan-
nel
10
Con-
trols
DO 9
Chan-
nel
9
Con-
trols
DO 8
Chan-
nel
8
Con-
trols
DO 7
Chan-
nel
7
Con-
trols
DO 6
Chan-
nel
6
Con-
trols
DO 5
Chan-
nel
5
Con-
trols
DO 4
Chan-
nel
4
Con-
trols
DO 3
Chan-
nel
3
Con-
trols
DO 2
Chan-
nel
2
Con-
trols
DO 1
Chan-
nel
1
Pos: 100.4 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Pos: 100.5 /Serie 750 ( WAGO-I/O-SYST EM)/Pr ozessabbild M appi ng/ETH ERNET - EtherNet/IP - M ODBU S/TC P/PA ETH ERN ET - AIs-Ei nlei tung MOD BUS/TCP (INTEL, mit word- alignment) @ 7\mod_1272352811572_21.docx @ 55815 @ 3 @ 1
12.2.4 Analog Input Modules
The hardware of an analog input module has 16 bits of measured analog data
per channel and 8 bits of control/status.
However, the coupler/controller with MODBUS/TCP does not have access to the
8 control/status bits.
Therefore, the coupler/controller with MODBUS/TCP can only access the 16 bits
of analog data per channel, which are grouped as words and mapped in Intel
format in the Input Process Image.
Pos: 100.6 /Serie 750 ( WAGO-I/O-SYST EM)/Pr ozessabbild M appi ng/Sofern i n dem Knoten auch Digital eingangsmodule gesteckt, zu AIs @ 8\mod_1279112061364_21.docx @ 59903 @ @ 1
When digital input modules are also present in the node, the analog input data is
always mapped into the Input Process Image in front of the digital data.
Pos: 100.7 /Serie 750 ( WAGO-I/O-SYST EM)/Pr ozessabbild M appi ng/Informati on - Informati onen zum Steuer-/Statusbyteaufbau @ 4\mod_1238055708743_21.docx @ 29070 @ @ 1
Information on the structure of control and status bytes
For detailed information on the structure of a particular I/O module’s
control/status bytes, please refer to that module’s manual. Manuals for each
module can be found on the Internet at
Pos: 100.8 /Serie 750 ( WAGO-I/O-SYST EM)/Pr ozessabbild M appi ng/ETH ERNET - EtherNet/IP - M ODBU S/TC P/PA ETH ERN ET - AIs XTR @ 16\mod_1374048837793_21.docx @ 126378 @ 444 @ 1
12.2.4.1 2-Channel Analog Input Modules
Table 265: 2-Channel Analog Input Modules
Input Process Image
Offset
Byte designation
Remark
High byte
Low byte
0
D1
D0
Measured value channel 1
1