WAGO-I/O-SYSTEM 750 XTR
I/O Modules 247
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
12.3.5.2 SSI Transmitter Interface I/O Modules
The process image depends on the parameterized operating mode!
The operating mode of the configurable I/O module can be set. Based on the
operating mode, the process image of these I/O modules is then the same as
that of the respective version.
In the input process image, SSI transmitter interface modules with status occupy
4 data bytes. Two words are assigned in the process image via word alignment.
Table 300: SSI transmitter interface modules with alternative data format
Input process image
Instance
Byte designation
Remark
High byte
Low byte
n
D1
D0
Data bytes
n+1
D3
D2
These specialty modules represent 2x2 bytes and occupy 2 instances in class
(0x67).
12.3.5.3 Distance and Angle Measurement
The incremental encoder interface I/O module appears with 6 bytes of reference
data in the input and output area of the process image, 4 data bytes and two
additional control/status bytes. Four words are assigned in the process image via
word alignment.
Table 301: Incremental Encoder Interface I/O module
Input and Output Process Image
Instance
Byte designation
Remark
High byte
Low byte
n
-
C0/S0
Control/status byte of channel 1
D1
D0
Data values of channel 1
n+1
-
C1/S1
Control/status byte of channel 2
D3
D2
Data values of channel 2
These specialty modules represent 2x3 bytes and occupy 2 instances in class
(0x67) and 2 instances in class (0x68).