WAGO-I/O-SYSTEM 750 XTR
Fieldbus Communication 169
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Register Access Writing (with FC6 and FC16)
Table 107: Register Access Writing (with FC6 and FC16)
MODBUS address
IEC 61131
Memory range
[dec]
[hex]
address
0...255
0x0000...0x00FF
%QW0...%QW255
Physical output area (1)
First 256 Words of physical output data
256...511
0x0100...0x01FF
-
MODBUS exception:
“Illegal data address”
512...767
0x0200...0x02FF
%QW0...%QW255
Physical output area (1)
First 256 Words of physical output data
768...4095
0x0300...0x0FFF
-
MODBUS exception:
“Illegal data address”
4096...12287 0x1000...0x2FFF
-
Configuration register (see Section
“Configuration Register”)
12288...24575 0x3000...0x5FFF
-
MODBUS exception:
“Illegal data address”
24576...25339 0x6000...0x62FB %QW256...%QW1020 Physical output area (2)
Additional 764 Words physical output data
25340...28671 0x62FC...0x6FFF
-
MODBUS exception:
“Illegal data address”
28672...29435 0x7000...0x72FB %QW256...%QW1020 Physical output area (2)
Additional 764 Words physical output data
29436...65535 0x72FC...0xFFFF
-
MODBUS exception:
“Illegal data address”
Pos: 94.21 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbeschrei bung/F eldbuskommuni kation/M ODBU S/MOD BU S-Register-Mappi ng - Absatz C oil-Dienste, Bitzugriffe @ 3\mod_1235393917265_21.docx @ 27584 @ @ 1
The digital MODBUS services (coil services) are bit accesses, with which only the
states of digital I/O modules can be determined or changed. Complex I/O
modules are not attainable with these services and so they are ignored. Because
of this the addressing of the digital channels begins again with 0, so that the
MODBUS address is always identical to the channel number, (i.e. the digital input
no. 47 has the MODBUS address "46").