104 Configuring via the Web-Based Management System (WBM)WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Pos: 69.1 /Serie 750 (WAGO-I/O-SYST EM)/Web-Based-Management-System WBM/Im Web-Based-Management- System konfigurier en (Ei nleitung und Überschrift 1) @ 4\mod_1242217768500_21.docx @ 33098 @ 1 @ 1
9
Configuring via the Web-Based Management
System (WBM)
An integrated Web server can be used for configuration and administration of the
device. The HTML pages together, they are referred to as the Web-based
Management System (WBM).
The presentation of these web pages takes place after a user registration for
access via a web browser (eg Microsoft Internet Explorer, Mozilla Firefox, etc).
For login, 3 different password-protected user authorization groups are provided
as standard:
Table 32: WBM User Groups
User Group
Default Password Access Rights
admin
wago
Read/write access to all WBM pages as
well as passwords modification and
CODESYS application download, if this
is enabled for CODESYS (WBM page
"Security"> "PLC Security "> "
CODESYS port authentication")
user
user
Read/write access to all WBM pages,
but no write authorization on WBM-page
"Security"
guest
guest
Read only
When closing the web browser, the user is automatically logged out and the
WBM session is closed.
The WBM pages saved internally provide current information about the
configuration and status of the device. In addition, it is possible to change the
configuration of the device here.
Also HTML pages created by yourself can be save via the implemented file
system.
Always restart after making changes to the configuration!
The system must always be restarted for the changed configuration settings to
take effect.
1.
To open the WBM, launch a Web browser.
2.
Enter the IP address of the fieldbus coupler/controller in the address bar.
3.
Click
[Enter]
to confirm.
The start page of WBM loads.
4.
Select the link to the desired WBM page in the left navigation bar.
A login dialog appears.