96 Commissioning
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Pos: 67.22.24 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbusknoten in Betrieb nehmen/WBM aufrufen - Anl eitung ( Koppler) @ 23\mod_1434976371286_21.docx @ 184288 @ @ 1
1.
Open the
Web browser
on your client (such as the Microsoft Internet
Explorer) to have the HTML pages displayed.
2.
Enter the
IP address
for your fieldbus node in the address line of the
browser and press
[Return]
.
3.
If a dialog window then appears with a password prompt, as Administrator,
enter the user name: "
admin
" and the password "
wago
".
This is provided for secure access and entails three different user groups:
admin, user and guest.
A start page is then displayed in the browser window with information about
your fieldbus coupler (start page can be changed on HTML page
“Security”).
You can navigate to other information using the hyperlinks in the left
navigation bar.
Pos: 67.22.25 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbusknoten in Betrieb nehmen/Klicken Si e i n der li nken N avigationsleiste auf den Li nk „ Por t“, um di e HTM L-Seite für die... @ 4\mod_1239109846656_21.docx @ 30255 @ @ 1
4.
In the left navigation bar click on
Port
to open the HTML page for selecting
a protocol.
Pos: 67.22.26 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbusknoten in Betrieb nehmen/Si e erhalten ei ne Liste aller Protokoll e, die der Koppl er unterstützt. (Koppler) @ 6\mod_1264493537441_21.docx @ 48690 @ @ 1
You are shown a list of all the protocols supported by the coupler.
Pos: 67.22.27 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbusknoten in Betrieb nehmen/Untergruppen/Wähl en Si e di e Option " use IP fr om EEPROM" - BootP deakti vieren @ 22\mod_1430745863672_21.docx @ 181688 @ @ 1
5.
Select the “use IP from EEPROM“ option.
At the same time disables the request of BootP server.
6.
Confirm your changes with button
[SUBMIT]
.
7.
Then restart in order for the settings to take effect.
Pos: 67.22.28 /Seri e 750 ( WAGO-I/O-SYSTEM)/In Betrieb nehmen/Fel dbusknoten in Betrieb nehmen/Untergruppen/Softwar e-Reset durchführen und mit neuer IP Br owser öffnen. @ 22\mod_1431076574867_21.docx @ 181918 @ @ 1
8.
For a restart, click in the left navigation bar on the link
[Security]
to open
the HTML page on which you can set passwords and trigger a software
reset.
9.
Click on the button
[Software Reset]
at the bottom of the page
.
Then the coupler/controller starts with the configurations, which were
previously loaded into the EEPROM and the connection to the browser is
interrupted.
10. Now you must use the changed IP address, if you want to access again on
this device via browser.