210 Fieldbus Communication
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Instance 0 (Class Attributes)
Table 198: Coupler/Controller configuration (64
hex
) – Class
Attribute ID Acces
s
Name
Data type Description
Default value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance UINT
Maximum number of
instances
1 (0x0001)
Instance 1
Table 199: Coupler/Controller configuration (64
hex
) – Instance 1
Attribute ID Acces
s
NV Name
Data type Description
Default
value
5
Get
V
ProcessStat
e
USINT
State of coupler/controller, error
mask:
Bit 0: Local bus error
Bit 3: Module diagnostics (0x08)
Bit 7: Fieldbus error (0x80)
0
6
Get
V
DNS_i_
Trmnldia
UINT
Module diagnostics:
Bit 0..7: Module number
Bit 8..14: Module channel
Bit 15: 0/1 Error, repair/arisen
0
7
Get
V
CnfLen.
AnalogOut
UINT
Number of I/O bits for the analog
output
-
8
Get
V
CnfLen.
AnalogInp
UINT
Number of I/O bits for the analog
input
-
9
Get
V
CnfLen.
DigitalOut
UINT
Number of I/O bits for the digital
output
-
10
Get
V
CnfLen.
DigitalInp
UINT
Number of I/O bits for the digital
input
-
11
Set
NV Bk_Fault_
Reaction
USINT
Fieldbus error reaction
0: stop local I/O cycles
1: set all output to 0
2: no error reaction
3: no error reaction
4: PFC task takes over control of
the outputs (apply to controllers)
1
12..26
Reserved for compatibility to DeviceNet
40..43
Reserved for compatibility to DeviceNet
45
Get
V
Bk_Led_Err
_Code
UINT
I/O LED error code
0
46
Get
V
Bk_Led_Err
_Arg
UINT
I/O LED error argument
0
Pos: 96.11 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbeschrei bung/F eldbuskommuni kation/EtherN etIP/C oupl erControll er C onfig urati on - AttributID 120, 121, C ommon ser vice @ 3\mod_1233831576390_21.docx @ 27222 @ @ 1