WAGO-I/O-SYSTEM 750 XTR
Device Description 63
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Table 26: EMC – Emission of Interference
Standard
Test Value
*)
Conducted Emission of Interference – Line Connection DC Voltage
• EN 61000-6-3
• EN 60255-26
• EN 55032 Class A
79 dB(µV) QP, 0.15 MHz … 0.5 MHz
66 dB(µV) AV, 0.15 MHz … 0.5 MHz
73 dB(µV) QP, 0.5 MHz … 30 MHz
60 dB(µV) AV, 0.5 MHz … 30 MHz
*)
QP = Quasi Peak Detector; AV = Average Detector
**)
If necessary, please find different data in the section “Approval” (regarding approval for
EMC A or EMC B).
Pos: 48.8 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung (alte Str uktur)/Nor men und Richtlini en/Nor men Störaussendung XTR - Tel ekommuni kationsanschl üsse @ 18\mod_1395059614663_21.docx @ 148078 @ @ 1
Table 27: EMC – Emission of Interference – Telecommunication Connections
Standard
Test Value
1)
Telecommunication Connections
• EN 61000-6-3
• EN 55032 Class B
84 dB(µV) … 74 dB(µV) QP
74 dB(µV) … 64 dB(µV) AV,
0.15 MHz … 0.5 MHz
74 dB(µV) … 64 dB(µV) QP,
0.5 MHz … 30 MHz
74 dB(µV) … 64 dB(µV) AV,
0.5 MHz … 30 MHz
• EN 61000-6-4
• EN 55032 Class A
97 dB(µV) … 87 dB(µV) QP,
0.15 MHz … 0.5 MHz
84 dB(µV) … 74 dB(µV) AV,
0.15 MHz … 0.5 MHz
87 dB(µV) QP, 0.5 MHz … 30 MHz
74 dB(µV) AV, 0.5 MHz … 30 MHz
1)
QP = Quasi Peak Detector; AV = Average Detector
*)
If necessary, please find different data in the section “Approval” (regarding approval for EMC 1 or
EMC 2).